HILL CREST MANOR
HAMILTON, MO · 90 certified beds · Last Life Safety survey May 7, 2026
CMS Certification Number 265665 · first certified January 1997
Ownership
Operated by CIRCLE B ENTERPRISES · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within MO
47 citations — more than 97% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 9 citations; the earlier surveys in the window averaged 19. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was May 2026. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about HILL CREST MANOR
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
3 of the 47 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0908 Keep all essential equipment working safely.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0924 Put firmly secured handrails on each side of hallways.
How that compares
Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 47 |
| Median facility in MO | 18 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| September 13, 2023 | 14 |
| January 29, 2025 | 24 |
| May 7, 2026 | 9 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-05-07 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 3 | 2026-05-07 |
| K-0161 | Use approved construction type or materials. | 3 | 2026-05-07 |
| K-0293 | Have properly located and lighted "Exit" signs. | 3 | 2026-05-07 |
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2025-01-29 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 2 | 2025-01-29 |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | 2 | 2026-05-07 |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | 2 | 2026-05-07 |
What the citations cover
- Smoke Deficiencies 18
- Egress Deficiencies 15
- Construction Deficiencies 5
- Gas, Vacuum, and Electrical Systems Deficiencies 4
- Other 5
| Category | Citations |
|---|---|
| Smoke Deficiencies | 18 |
| Egress Deficiencies | 15 |
| Construction Deficiencies | 5 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 4 |
| Emergency Preparedness Deficiencies | 3 |
| Services Deficiencies | 1 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 7, 2026 — 9 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | No revisit needed (November 7, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 8, 2026) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (July 8, 2026) |
January 29, 2025 — 24 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. | Deficient, Provider has no plan of correction |
| K-0131 | Meet requirements for sections of health care facilities separated by fire resistive construction. | Deficient, Provider has no plan of correction |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0200 | Meet other general requirements. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has no plan of correction |
| K-0251 | Conform to length requirements for dead end corridors. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has no plan of correction |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has no plan of correction |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0362 | Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has no plan of correction |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (March 12, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (March 12, 2025) |
September 13, 2023 — 14 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Waiver has been granted (October 18, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Waiver has been granted (October 18, 2023) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (October 28, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (October 28, 2023) |