Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

HILL CREST MANOR

HAMILTON, MO · 90 certified beds · Last Life Safety survey May 7, 2026

CMS Certification Number 265665 · first certified January 1997

Ownership

Operated by CIRCLE B ENTERPRISES · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

47
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
12
Inspection & testing records
Of the citations on file

Position within MO

47 citations — more than 97% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 19. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was May 2026. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about HILL CREST MANOR

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 47 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 47 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0924 Put firmly secured handrails on each side of hallways.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility47MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility47
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
142023-09242025-0192026-05
Citations at each Life Safety survey
Survey dateCitations
September 13, 202314
January 29, 202524
May 7, 20269

Most-cited tags

Most-cited tags at this facility
K-03533K-02113K-01613K-02933K-03632K-03212K-02232K-03742
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-05-07
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32026-05-07
K-0161Use approved construction type or materials.32026-05-07
K-0293Have properly located and lighted "Exit" signs.32026-05-07
K-0363Install corridor and hallway doors that block smoke.22025-01-29
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22025-01-29
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.22026-05-07
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22026-05-07

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Egress Deficiencies 15
  • Construction Deficiencies 5
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Egress Deficiencies15
Construction Deficiencies5
Gas, Vacuum, and Electrical Systems Deficiencies4
Emergency Preparedness Deficiencies3
Services Deficiencies1
Miscellaneous Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 7, 2026 — 9 citations

Citations issued on May 7, 2026
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (July 8, 2026)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 8, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.No revisit needed (November 7, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 8, 2026)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (July 8, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 8, 2026)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (July 8, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 8, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (July 8, 2026)

January 29, 2025 — 24 citations

Citations issued on January 29, 2025
TagWhat the surveyor checksStatus
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (March 12, 2025)
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has no plan of correction
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has no plan of correction
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 12, 2025)
K-0200Meet other general requirements.Deficient, Provider has date of correction (March 12, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 12, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has no plan of correction
K-0251Conform to length requirements for dead end corridors.Deficient, Provider has date of correction (March 12, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has no plan of correction
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 12, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 12, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (March 12, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has no plan of correction
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 12, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 12, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 12, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 12, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (March 12, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 12, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has no plan of correction
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 12, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (March 12, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 12, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 12, 2025)

September 13, 2023 — 14 citations

Citations issued on September 13, 2023
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 28, 2023)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (October 28, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 28, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 28, 2023)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (October 28, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 28, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted (October 18, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 28, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 28, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (October 18, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 28, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 28, 2023)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (October 28, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 28, 2023)