Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BELOVED HEALTH AND REHABILITATION CENTER

HANNIBAL, MO · 111 certified beds · Last Life Safety survey November 27, 2024

CMS Certification Number 265462 · first certified August 1991

Ownership

Independently operated (no chain recorded by CMS) · For profit - Individual

  • Ownership changed November 1, 2022 (change of ownership)from TUTERA ACQUIRERS, INC
52
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within MO

52 citations — more than 99% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 25 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (January 2026 to August 2026). Most MO facilities have been surveyed by October 2026. This facility’s last Life Safety survey was November 2024. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about BELOVED HEALTH AND REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

18 of the 52 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

18 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 52 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility52MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility52
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-05182022-12252024-11
Citations at each Life Safety survey
Survey dateCitations
May 2, 20199
December 7, 202218
November 27, 202425

Most-cited tags

Most-cited tags at this facility
K-03243E-00203K-03723K-07413K-03213E-00132E-00262E-00412
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0324Provide properly protected cooking facilities.32024-11-27
E-0020Establish policies and procedures including evacuation.32024-11-27
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32024-11-27
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32024-11-27
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-11-27
E-0013Develop Emergency Preparedness policies and procedures.22024-11-27
E-0026Establish roles under a Waiver declared by secretary.22024-11-27
E-0041Implement emergency and standby power systems.22024-11-27

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 18
  • Smoke Deficiencies 16
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Miscellaneous Deficiencies 5
  • Other 4
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies18
Smoke Deficiencies16
Gas, Vacuum, and Electrical Systems Deficiencies9
Miscellaneous Deficiencies5
Construction Deficiencies2
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 27, 2024 — 25 citations

Citations issued on November 27, 2024
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (January 13, 2025)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (January 13, 2025)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (January 13, 2025)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (January 13, 2025)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (January 13, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (January 13, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (January 13, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (January 13, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (January 13, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 13, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 13, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 13, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 13, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 13, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (January 13, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 17, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 13, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 13, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 13, 2025)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (January 13, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 13, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (January 13, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 13, 2025)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (January 13, 2025)

December 7, 2022 — 18 citations

Citations issued on December 7, 2022
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (January 21, 2023)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (January 21, 2023)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (January 21, 2023)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (January 21, 2023)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (January 21, 2023)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (January 21, 2023)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (January 21, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (January 21, 2023)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (January 21, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 21, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (January 21, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 21, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 21, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 21, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 21, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 21, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 21, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 21, 2023)

May 2, 2019 — 9 citations

Citations issued on May 2, 2019
TagWhat the surveyor checksStatus
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (June 12, 2019)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (June 12, 2019)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (June 12, 2019)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 12, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 12, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 12, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 12, 2019)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 12, 2019)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 12, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.