Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

RIVER CITY LIVING COMMUNITY

JEFFERSON CITY, MO · 87 certified beds · Last Life Safety survey October 4, 2024

CMS Certification Number 265482 · first certified March 1992

Ownership

Operated by JAMES & JUDY LINCOLN · For profit - Corporation

  • Ownership changed September 1, 2016 (change of ownership)from GGNSC JEFFERSON CITY LLC
48
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
15
Tags cited more than once
Across separate surveys
21
Inspection & testing records
Of the citations on file

Position within MO

48 citations — more than 98% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 18 citations; the earlier surveys in the window averaged 15. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (December 2025 to June 2026), and past the point by which nine in ten MO facilities have been surveyed. This facility’s last Life Safety survey was October 2024. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about RIVER CITY LIVING COMMUNITY

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 48 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 48 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility48MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility48
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
102019-08202023-01182024-10
Citations at each Life Safety survey
Survey dateCitations
August 2, 201910
January 12, 202320
October 4, 202418

Most-cited tags

Most-cited tags at this facility
K-07123K-03533K-09183K-03743E-00373K-09142K-03542K-02712
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32024-10-04
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-10-04
K-0918Have generator or other power source capable of supplying service within 10 seconds.32024-10-04
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.32024-10-04
E-0037Establish staff and initial training requirements.32024-10-04
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22023-01-12
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.22024-10-04
K-0271Have exits that are accessible at all times.22024-10-04

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 21
  • Gas, Vacuum, and Electrical Systems Deficiencies 10
  • Emergency Preparedness Deficiencies 6
  • Miscellaneous Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies21
Gas, Vacuum, and Electrical Systems Deficiencies10
Emergency Preparedness Deficiencies6
Miscellaneous Deficiencies5
Egress Deficiencies5
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

October 4, 2024 — 18 citations

Citations issued on October 4, 2024
TagWhat the surveyor checksStatus
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (November 15, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (November 15, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (November 15, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (November 15, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (November 15, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 15, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (November 15, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (November 15, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 15, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 15, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (November 15, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 15, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 15, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 15, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 15, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 15, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (November 15, 2024)

January 12, 2023 — 20 citations

Citations issued on January 12, 2023
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (February 22, 2023)
K-0100Meet other general requirements.Deficient, Provider has date of correction (February 22, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (February 22, 2023)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (February 22, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 22, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (February 22, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 22, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 22, 2023)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (February 22, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 22, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (February 22, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 22, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 22, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 22, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 22, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 22, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (February 22, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 22, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 22, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 22, 2023)

August 2, 2019 — 10 citations

Citations issued on August 2, 2019
TagWhat the surveyor checksStatus
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (September 12, 2019)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (September 12, 2019)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (September 12, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 12, 2019)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 12, 2019)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 12, 2019)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 12, 2019)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 12, 2019)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 12, 2019)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 12, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.