Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

ASPIRE SENIOR LIVING POPLAR BLUFF

POPLAR BLUFF, MO · 83 certified beds · Last Life Safety survey April 23, 2026

CMS Certification Number 265450 · first certified March 1991

Ownership

Operated by ASPIRE SENIOR LIVING · For profit - Limited Liability company

  • Ownership changed June 1, 2024 (change of ownership)from N & R OF POPLAR BLUFF, INC.
13
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
6
Inspection & testing records
Of the citations on file

Position within MO

13 citations — more than 33% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 3. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 9 months from now. This facility’s last Life Safety survey was April 2026. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about ASPIRE SENIOR LIVING POPLAR BLUFF

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 13 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility13MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility13
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
42023-1222025-0172026-04
Citations at each Life Safety survey
Survey dateCitations
December 1, 20234
January 9, 20252
April 23, 20267

Most-cited tags

Most-cited tags at this facility
K-09202K-03242K-03211K-09111K-02231K-03531K-02111K-03511
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0920Ensure proper usage of power strips and extension cords.22026-04-23
K-0324Provide properly protected cooking facilities.22026-04-23
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12026-04-23
K-0911Meet requirements for the installation and maintenance of electrical systems.12026-04-23
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.12023-12-01
K-0353Inspect, test, and maintain automatic sprinkler systems.12026-04-23
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.12025-01-09
K-0351Install an approved automatic sprinkler system.12026-04-23

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Egress Deficiencies 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies4
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 23, 2026 — 7 citations

Citations issued on April 23, 2026
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 7, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 7, 2026)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 7, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 7, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 7, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (June 7, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 7, 2026)

January 9, 2025 — 2 citations

Citations issued on January 9, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (February 23, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 23, 2025)

December 1, 2023 — 4 citations

Citations issued on December 1, 2023
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (January 15, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 15, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 15, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 15, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.