ST JAMES LIVING CENTER

SAINT JAMES, MO · 90 certified beds · Last Life Safety survey November 17, 2025

CMS Certification Number 265225 · first certified February 1984

Ownership

Operated by JAMES & JUDY LINCOLN · For profit - Corporation

  • Ownership changed September 1, 2016 (change of ownership)from GGNSC ST. JAMES LLC
34
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
9
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within MO

34 citations — more than 86% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 15.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was November 2025. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about ST JAMES LIVING CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

4 of the 34 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 34 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility34MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility34
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
152023-06162024-0732025-11
Citations at each Life Safety survey
Survey dateCitations
June 2, 202315
July 17, 202416
November 17, 20253

Most-cited tags

Most-cited tags at this facility
K-03533K-07123K-03722K-09182K-09232K-03632K-02222K-03452
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-17
K-0712Have simulated fire drills held at unexpected times.32025-11-17
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22025-11-17
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-07-17
K-0923Have proper medical gas storage and administration areas.22024-07-17
K-0363Install corridor and hallway doors that block smoke.22024-07-17
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22024-07-17
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22024-07-17

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Miscellaneous Deficiencies 6
  • Emergency Preparedness Deficiencies 4
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies6
Emergency Preparedness Deficiencies4
Egress Deficiencies4
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 17, 2025 — 3 citations

Citations issued on November 17, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 31, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 31, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 31, 2025)

July 17, 2024 — 16 citations

Citations issued on July 17, 2024
TagWhat the surveyor checksStatus
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (August 30, 2024)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 30, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 30, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 30, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 30, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 30, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 30, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 30, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 30, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 30, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 30, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 30, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (August 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 30, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 30, 2024)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (August 30, 2024)

June 2, 2023 — 15 citations

Citations issued on June 2, 2023
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (July 16, 2023)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (July 16, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (July 16, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 16, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 16, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 16, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 16, 2023)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (July 16, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 16, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 16, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 16, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 16, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 16, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 16, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 16, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.