Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CHRISTIAN EXTENDED CARE & REHABILITATION

SAINT LOUIS, MO · 60 certified beds · Last Life Safety survey March 28, 2025

CMS Certification Number 265174 · first certified September 1982

Ownership

Operated by BJC HEALTHCARE · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

13
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
1
Tags cited more than once
Across separate surveys
10
Inspection & testing records
Of the citations on file

Position within MO

13 citations — more than 33% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 4 citations; the earlier surveys in the window averaged 4.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: May 2026 to December 2026. This facility’s last Life Safety survey was March 2025. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CHRISTIAN EXTENDED CARE & REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 13 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 13 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility13MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility13
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
22020-0972023-1042025-03
Citations at each Life Safety survey
Survey dateCitations
September 23, 20202
October 13, 20237
March 28, 20254

Most-cited tags

Most-cited tags at this facility
K-03532K-03241K-05111K-03721K-07611K-03551K-03451K-03511
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-03-28
K-0324Provide properly protected cooking facilities.12023-10-13
K-0511Have properly installed electrical wiring and gas equipment.12025-03-28
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12023-10-13
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.12023-10-13
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12025-03-28
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12023-10-13
K-0351Install an approved automatic sprinkler system.12023-10-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 7
  • Miscellaneous Deficiencies 2
  • Services Deficiencies 1
  • Egress Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies7
Miscellaneous Deficiencies2
Services Deficiencies1
Egress Deficiencies1
Emergency Preparedness Deficiencies1
Gas, Vacuum, and Electrical Systems Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 28, 2025 — 4 citations

Citations issued on March 28, 2025
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (May 2, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 2, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 2, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 2, 2025)

October 13, 2023 — 7 citations

Citations issued on October 13, 2023
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (November 10, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 10, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 10, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (November 29, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 10, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 10, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 10, 2023)

September 23, 2020 — 2 citations

Citations issued on September 23, 2020
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 31, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 10, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.