Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

OAK PARK CARE CENTER

SAINT LOUIS, MO · 120 certified beds · Last Life Safety survey August 14, 2024

CMS Certification Number 265427 · first certified April 1990

Ownership

Operated by MGM HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

49
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within MO

49 citations — more than 98% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 19.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (October 2025 to May 2026), and past the point by which nine in ten MO facilities have been surveyed. This facility’s last Life Safety survey was August 2024. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about OAK PARK CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 49 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 49 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0924 Put firmly secured handrails on each side of hallways.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility49MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility49
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-07302023-01102024-08
Citations at each Life Safety survey
Survey dateCitations
July 22, 20199
January 27, 202330
August 14, 202410

Most-cited tags

Most-cited tags at this facility
K-03723K-07123K-09143K-03533K-02112K-03212K-03242K-01612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32024-08-14
K-0712Have simulated fire drills held at unexpected times.32024-08-14
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.32024-08-14
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-08-14
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22023-01-27
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22023-01-27
K-0324Provide properly protected cooking facilities.22024-08-14
K-0161Use approved construction type or materials.22024-08-14

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 21
  • Egress Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Emergency Preparedness Deficiencies 5
  • Other 11
Citations by CMS category
CategoryCitations
Smoke Deficiencies21
Egress Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies5
Emergency Preparedness Deficiencies5
Miscellaneous Deficiencies5
Services Deficiencies3
Construction Deficiencies2
Electrical Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 14, 2024 — 10 citations

Citations issued on August 14, 2024
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (September 18, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (September 18, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 18, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 18, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (September 18, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 18, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 18, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (September 18, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 18, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 18, 2024)

January 27, 2023 — 30 citations

Citations issued on January 27, 2023
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (March 8, 2023)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (March 8, 2023)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (March 8, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (March 8, 2023)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 8, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 8, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 16, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 8, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 8, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (March 8, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 8, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 8, 2023)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (March 8, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 8, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted (March 8, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (March 8, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 8, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 8, 2023)
K-0364Install properly constructed windows in hallway walls or doors.Deficient, Provider has date of correction (March 8, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 16, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 8, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 8, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Waiver has been granted (March 8, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 16, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 8, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 8, 2023)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (March 17, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 8, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 8, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (March 17, 2023)

July 22, 2019 — 9 citations

Citations issued on July 22, 2019
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 28, 2019)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 28, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 28, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 28, 2019)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 28, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 28, 2019)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Waiver has been granted (January 22, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 28, 2019)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 28, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.