Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

CHARITON PARK HEALTH CARE CENTER

SALISBURY, MO · 120 certified beds · Last Life Safety survey April 30, 2026

CMS Certification Number 265526 · first certified March 1993

Ownership

Operated by RELIANT CARE MANAGEMENT · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

42
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
8
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within MO

42 citations — more than 94% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 8 citations; the earlier surveys in the window averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 9 months from now. This facility’s last Life Safety survey was April 2026. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about CHARITON PARK HEALTH CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

10 of the 42 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 42 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility42MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility42
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
192022-05152024-0382026-04
Citations at each Life Safety survey
Survey dateCitations
May 19, 202219
March 8, 202415
April 30, 20268

Most-cited tags

Most-cited tags at this facility
K-07413K-09203K-03633K-03743K-03722K-02912K-03242K-03532
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32026-04-30
K-0920Ensure proper usage of power strips and extension cords.32026-04-30
K-0363Install corridor and hallway doors that block smoke.32026-04-30
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.32026-04-30
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-03-08
K-0291Install emergency lighting that can last at least 1 1/2 hours.22026-04-30
K-0324Provide properly protected cooking facilities.22024-03-08
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-03-08

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Emergency Preparedness Deficiencies 10
  • Egress Deficiencies 5
  • Miscellaneous Deficiencies 4
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Emergency Preparedness Deficiencies10
Egress Deficiencies5
Miscellaneous Deficiencies4
Gas, Vacuum, and Electrical Systems Deficiencies4
Construction Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

April 30, 2026 — 8 citations

Citations issued on April 30, 2026
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 3, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 3, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 3, 2026)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (June 3, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 3, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 3, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 3, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 3, 2026)

March 8, 2024 — 15 citations

Citations issued on March 8, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (April 19, 2024)
E-0033Establish methods for sharing information.Deficient, Provider has date of correction (April 19, 2024)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (April 19, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 13, 2024)
K-0100Meet other general requirements.Deficient, Provider has date of correction (April 19, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 19, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 19, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (April 19, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 19, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (June 13, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 13, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 13, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 13, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 19, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 19, 2024)

May 19, 2022 — 19 citations

Citations issued on May 19, 2022
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (July 11, 2022)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (July 11, 2022)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (July 11, 2022)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (July 11, 2022)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (July 11, 2022)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (July 11, 2022)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 11, 2022)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (July 11, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 11, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 11, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 11, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 11, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Waiver has been granted (November 1, 2022)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (July 11, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 11, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 11, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 11, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 11, 2022)
K-0932Meet other general requirements.Deficient, Provider has date of correction (July 11, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.