Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

SPRINGFIELD SKILLED CARE CENTER

SPRINGFIELD, MO · 120 certified beds · Last Life Safety survey February 13, 2025

CMS Certification Number 265477 · first certified November 1991

Ownership

Operated by MGM HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

44
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within MO

44 citations — more than 96% of the 487 certified nursing homes in MO. Compared within MO rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 18 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: April 2026 to October 2026. This facility’s last Life Safety survey was February 2025. Facilities in MO are typically surveyed 14–21 months after the last one (median 17), measured over 567 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about SPRINGFIELD SKILLED CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 44 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

22 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in MO, and nationally. Surveyors differ markedly between states, so the MO figure is the meaningful one.

This facility44MO median18National median11
Citations on file over three years, compared
MeasureCitations
This facility44
Median facility in MO18
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-11172023-02182025-02
Citations at each Life Safety survey
Survey dateCitations
November 26, 20199
February 3, 202317
February 13, 202518

Most-cited tags

Most-cited tags at this facility
K-02223K-09233K-03453K-07413K-01613K-09142K-09182K-07612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32025-02-13
K-0923Have proper medical gas storage and administration areas.32025-02-13
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-02-13
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32025-02-13
K-0161Use approved construction type or materials.32025-02-13
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22025-02-13
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-02-13
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22025-02-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Gas, Vacuum, and Electrical Systems Deficiencies 11
  • Miscellaneous Deficiencies 7
  • Egress Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Gas, Vacuum, and Electrical Systems Deficiencies11
Miscellaneous Deficiencies7
Egress Deficiencies5
Construction Deficiencies4
Services Deficiencies1
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 13, 2025 — 18 citations

Citations issued on February 13, 2025
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (March 26, 2025)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (February 28, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 28, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 28, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (February 28, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 20, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 21, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 17, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (March 7, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 28, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 28, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 28, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (February 28, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 22, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (May 2, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 28, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 28, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 28, 2025)

February 3, 2023 — 17 citations

Citations issued on February 3, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 5, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 5, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 15, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 5, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 1, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (March 15, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 3, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 3, 2023)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (February 22, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 15, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 1, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 22, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (March 5, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (February 15, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 15, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 15, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 20, 2023)

November 26, 2019 — 9 citations

Citations issued on November 26, 2019
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (January 10, 2020)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (January 10, 2020)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 10, 2020)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (January 10, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 7, 2020)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (January 10, 2020)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 10, 2020)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (January 10, 2020)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 10, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.