Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

COONEY HEALTHCARE AND REHABILITATION

HELENA, MT · 90 certified beds · Last Life Safety survey September 11, 2025

CMS Certification Number 275080 · first certified May 1977

Ownership

Operated by EDURO HEALTHCARE · For profit - Limited Liability company

  • Ownership changed October 1, 2020 (change of ownership)from COONEY HEALTH CARE INC
40
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within MT

40 citations — more than 98% of the 61 certified nursing homes in MT. Compared within MT rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 16 citations; the earlier surveys in the window averaged 8. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: September 2026 to October 2026. This facility’s last Life Safety survey was September 2025. Facilities in MT are typically surveyed 12–13 months after the last one (median 12), measured over 104 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about COONEY HEALTHCARE AND REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in MT, and nationally. Surveyors differ markedly between states, so the MT figure is the meaningful one.

This facility40MT median15National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in MT15
Median facility nationally11

Survey history

Citations at each Life Safety survey
42023-08152024-0852024-10162025-09
Citations at each Life Safety survey
Survey dateCitations
August 17, 20234
August 15, 202415
October 8, 20245
September 11, 202516

Most-cited tags

Most-cited tags at this facility
K-02113K-03213K-03533K-07122K-03242K-03742K-09232K-07612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32025-09-11
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-09-11
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-09-11
K-0712Have simulated fire drills held at unexpected times.22025-09-11
K-0324Provide properly protected cooking facilities.22025-09-11
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22024-10-08
K-0923Have proper medical gas storage and administration areas.22025-09-11
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22025-09-11

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 18
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 5
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies18
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies7
Miscellaneous Deficiencies5
Emergency Preparedness Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

September 11, 2025 — 16 citations

Citations issued on September 11, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 12, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 17, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (November 25, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 24, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 17, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (December 9, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 24, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (November 18, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 19, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 18, 2025)
K-0771Ensure that smoke control systems are tested and documented in accordance with established engineering principles.Deficient, Provider has plan of correction (October 24, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (December 12, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 24, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 12, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (December 9, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 18, 2025)

October 8, 2024 — 5 citations

Citations issued on October 8, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 25, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 25, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 25, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (October 25, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (October 25, 2024)

August 15, 2024 — 15 citations

Citations issued on August 15, 2024
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (September 11, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (September 6, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 6, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 6, 2024)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (September 6, 2024)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (September 6, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 6, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 6, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 6, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 6, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 6, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 6, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 6, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 6, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 6, 2024)

August 17, 2023 — 4 citations

Citations issued on August 17, 2023
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 1, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 1, 2023)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (October 1, 2023)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has date of correction (October 1, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.