Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Piedmont Hills Center for Nursing and Rehab

Greensboro, NC · 126 certified beds · Last Life Safety survey February 27, 2026

CMS Certification Number 345116 · first certified December 1980

Ownership

Operated by ALLIANCE HEALTH GROUP · For profit - Limited Liability company

  • Ownership changed August 1, 2024 (change of ownership)to PIEDMONT HILLS CENTER FOR NURSING AND REHABILITATION from CAROLINA PINES AT GREENSBORO LLC
40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within NC

40 citations — more than 100% of the 419 certified nursing homes in NC. Compared within NC rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens April 2027 — about 7 months from now. This facility’s last Life Safety survey was February 2026. Facilities in NC are typically surveyed 14–16 months after the last one (median 15), measured over 412 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Piedmont Hills Center for Nursing and Rehab

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NC, and nationally. Surveyors differ markedly between states, so the NC figure is the meaningful one.

This facility40NC median9National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in NC9
Median facility nationally11

Survey history

Citations at each Life Safety survey
182023-12102024-12122026-02
Citations at each Life Safety survey
Survey dateCitations
December 4, 202318
December 5, 202410
February 27, 202612

Most-cited tags

Most-cited tags at this facility
K-03633K-09183K-03213K-03722K-01612K-09142K-05312K-02112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.32026-02-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-02-27
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-02-27
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-02-27
K-0161Use approved construction type or materials.22026-02-27
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22026-02-27
K-0531Have elevators that firefighters can control in the event of a fire.22026-02-27
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22026-02-27

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 6
  • Services Deficiencies 5
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies6
Services Deficiencies5
Construction Deficiencies3
Miscellaneous Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 27, 2026 — 12 citations

Citations issued on February 27, 2026
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has plan of correction (August 14, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has plan of correction (August 14, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has plan of correction (August 14, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has plan of correction (August 14, 2026)
K-0342Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.Deficient, Provider has plan of correction (August 14, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction (August 14, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has plan of correction (August 14, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has plan of correction (August 14, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has plan of correction (August 14, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has plan of correction (August 14, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has plan of correction (August 14, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has plan of correction (August 14, 2026)

December 5, 2024 — 10 citations

Citations issued on December 5, 2024
TagWhat the surveyor checksStatus
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (April 17, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 17, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 17, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 17, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 17, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (April 17, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 17, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (April 17, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 17, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 17, 2025)

December 4, 2023 — 18 citations

Citations issued on December 4, 2023
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (March 20, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (March 20, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 20, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (March 20, 2024)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (March 20, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (March 20, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 20, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 20, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 20, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 20, 2024)
K-0364Install properly constructed windows in hallway walls or doors.Deficient, Provider has date of correction (March 20, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 20, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (March 20, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (March 20, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (March 20, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (March 20, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 20, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 20, 2024)