Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Kannapolis Health and Rehabilitation

Kannapolis, NC · 107 certified beds · Last Life Safety survey March 18, 2026

CMS Certification Number 345258 · first certified April 1987

Ownership

Operated by AVARDIS HEALTH · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

29
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
8
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within NC

29 citations — more than 98% of the 419 certified nursing homes in NC. Compared within NC rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 9 citations; the earlier surveys on file averaged 10. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens May 2027 — about 6 months from now. This facility’s last Life Safety survey was March 2026. Facilities in NC are typically surveyed 14–15 months after the last one (median 14), measured over 458 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about Kannapolis Health and Rehabilitation

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 29 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations in CMS's current file

Compared with the median facility in NC, and nationally. Surveyors differ markedly between states, so the NC figure is the meaningful one.

This facility29NC median10National median11
Citations in CMS's current file, compared
MeasureCitations
This facility29
Median facility in NC10
Median facility nationally11

Survey history

Citations at each Life Safety survey
52023-08152025-0192026-03
Citations at each Life Safety survey
Survey dateCitations
August 10, 20235
January 16, 202515
March 18, 20269

Most-cited tags

Most-cited tags at this facility
K-03213K-07123K-09183K-03533K-03722K-02222K-01612K-05112
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-03-18
K-0712Have simulated fire drills held at unexpected times.32026-03-18
K-0918Have generator or other power source capable of supplying service within 10 seconds.32026-03-18
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-03-18
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-03-18
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22026-03-18
K-0161Use approved construction type or materials.22026-03-18
K-0511Have properly installed electrical wiring and gas equipment.22026-03-18

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Egress Deficiencies 4
  • Miscellaneous Deficiencies 4
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies5
Egress Deficiencies4
Miscellaneous Deficiencies4
Services Deficiencies3
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 18, 2026 — 9 citations

Citations issued on March 18, 2026
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 31, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 31, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 31, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 31, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 31, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 31, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 31, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 31, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 31, 2026)

January 16, 2025 — 15 citations

Citations issued on January 16, 2025
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (May 19, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 19, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (May 19, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (May 19, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 19, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (May 19, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 19, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 19, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 19, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 19, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (May 19, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 19, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (May 19, 2025)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (May 19, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 19, 2025)

August 10, 2023 — 5 citations

Citations issued on August 10, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 17, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 17, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 17, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (October 17, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 17, 2023)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.