Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Gateway Vista

Lincoln, NE · 80 certified beds · Last Life Safety survey September 3, 2025

CMS Certification Number 285266 · first certified March 2005

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

43
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
12
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within NE

43 citations — more than 95% of the 180 certified nursing homes in NE. Compared within NE rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 16 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: September 2026 to November 2026. This facility’s last Life Safety survey was September 2025. Facilities in NE are typically surveyed 12–14 months after the last one (median 13), measured over 271 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Gateway Vista

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 43 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 43 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0923 Have enough outside ventilation via a window or mechanical ventilation, or both.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in NE, and nationally. Surveyors differ markedly between states, so the NE figure is the meaningful one.

This facility43NE median15National median11
Citations on file over three years, compared
MeasureCitations
This facility43
Median facility in NE15
Median facility nationally11

Survey history

Citations at each Life Safety survey
182023-0792024-06162025-09
Citations at each Life Safety survey
Survey dateCitations
July 13, 202318
June 12, 20249
September 3, 202516

Most-cited tags

Most-cited tags at this facility
K-02223K-03213K-03533K-07123K-05003K-09202K-09192K-09222
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32025-09-03
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32025-09-03
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-09-03
K-0712Have simulated fire drills held at unexpected times.32025-09-03
K-0500Meet other general requirements that are deficient.32025-09-03
K-0920Ensure proper usage of power strips and extension cords.22024-06-12
K-0919Meet requirements for the use of electrical equipment.22025-09-03
K-0922Meet requirements for the use and maintenance of medical gas equipment.22025-09-03

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Gas, Vacuum, and Electrical Systems Deficiencies 12
  • Egress Deficiencies 8
  • Miscellaneous Deficiencies 5
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Gas, Vacuum, and Electrical Systems Deficiencies12
Egress Deficiencies8
Miscellaneous Deficiencies5
Services Deficiencies3
Emergency Preparedness Deficiencies2
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

September 3, 2025 — 16 citations

Citations issued on September 3, 2025
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 18, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 18, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 18, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 18, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (October 18, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 18, 2025)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 18, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 18, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 18, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 18, 2025)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (October 18, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 18, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 18, 2025)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (October 18, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 18, 2025)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (October 18, 2025)

June 12, 2024 — 9 citations

Citations issued on June 12, 2024
TagWhat the surveyor checksStatus
K-0132Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.Deficient, Provider has date of correction (July 27, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 27, 2024)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (July 27, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 27, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 27, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (July 27, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 27, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 27, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 27, 2024)

July 13, 2023 — 18 citations

Citations issued on July 13, 2023
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (August 25, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 25, 2023)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (August 25, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 25, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 25, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 25, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 25, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (August 25, 2023)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (August 25, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (August 25, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 25, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (August 25, 2023)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (August 25, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 25, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 25, 2023)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (August 25, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 25, 2023)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (August 25, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.