Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Brookestone of Papillion

Papillion, NE · 110 certified beds · Last Life Safety survey February 20, 2025

CMS Certification Number 285268 · first certified May 2005

Ownership

Operated by VETTER SENIOR LIVING · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

21
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within NE

21 citations — more than 70% of the 180 certified nursing homes in NE. Compared within NE rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 0 citations; the earlier surveys in the window averaged 10.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (February 2026 to April 2026), and past the point by which nine in ten NE facilities have been surveyed. This facility’s last Life Safety survey was February 2025. Facilities in NE are typically surveyed 12–14 months after the last one (median 13), measured over 271 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Brookestone of Papillion

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 21 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 21 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NE, and nationally. Surveyors differ markedly between states, so the NE figure is the meaningful one.

This facility21NE median15National median11
Citations on file over three years, compared
MeasureCitations
This facility21
Median facility in NE15
Median facility nationally11

Survey history

Citations at each Life Safety survey
152022-1162023-1102025-02
Citations at each Life Safety survey
Survey dateCitations
November 8, 202215
November 2, 20236
February 20, 20250

Most-cited tags

Most-cited tags at this facility
K-03212K-07612K-03471K-03631K-09191K-09221K-07121K-03241
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22023-11-02
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22023-11-02
K-0347Properly provide smoke detection systems in areas open to corridors.12023-11-02
K-0363Install corridor and hallway doors that block smoke.12022-11-08
K-0919Meet requirements for the use of electrical equipment.12022-11-08
K-0922Meet requirements for the use and maintenance of medical gas equipment.12022-11-08
K-0712Have simulated fire drills held at unexpected times.12022-11-08
K-0324Provide properly protected cooking facilities.12022-11-08

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Egress Deficiencies 3
  • Miscellaneous Deficiencies 3
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies5
Egress Deficiencies3
Miscellaneous Deficiencies3
Construction Deficiencies1
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 2, 2023 — 6 citations

Citations issued on November 2, 2023
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (December 8, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 8, 2023)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (December 8, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (December 8, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 8, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (December 8, 2023)

November 8, 2022 — 15 citations

Citations issued on November 8, 2022
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 5, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (December 5, 2022)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 5, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (December 5, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 5, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (December 5, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 5, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 5, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 5, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 5, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 5, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (December 5, 2022)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (December 5, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (December 5, 2022)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (December 5, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.