Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

OAKS AT DENVILLE, THE

DENVILLE, NJ · 84 certified beds · Last Life Safety survey May 22, 2026

CMS Certification Number 315329 · first certified February 1994

Ownership

Operated by SPRINGPOINT SENIOR LIVING · Non profit - Corporation

  • Ownership changed May 6, 2016 (change of ownership)to THE OAKS AT DENVILLE from ST. FRANCIS LIFE CARE CORPORATION
28
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
5
Tags cited more than once
Across separate surveys
11
Inspection & testing records
Of the citations on file

Position within NJ

28 citations — more than 91% of the 348 certified nursing homes in NJ. Compared within NJ rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 8 citations; the earlier surveys on file averaged 10. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens September 2027 — about 10 months from now. This facility’s last Life Safety survey was May 2026. Facilities in NJ are typically surveyed 16–19 months after the last one (median 17), measured over 464 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about OAKS AT DENVILLE, THE

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 28 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 28 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in NJ, and nationally. Surveyors differ markedly between states, so the NJ figure is the meaningful one.

This facility28NJ median15National median11
Citations in CMS's current file, compared
MeasureCitations
This facility28
Median facility in NJ15
Median facility nationally11

Survey history

Citations at each Life Safety survey
62023-11142025-0182026-05
Citations at each Life Safety survey
Survey dateCitations
November 8, 20236
January 31, 202514
May 22, 20268

Most-cited tags

Most-cited tags at this facility
K-02912K-03532K-09122K-09202K-07122K-03551K-02221K-05211
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-01-31
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-01-31
K-0912Have power receptacles that are properly grounded.22026-05-22
K-0920Ensure proper usage of power strips and extension cords.22026-05-22
K-0712Have simulated fire drills held at unexpected times.22026-05-22
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12026-05-22
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12026-05-22
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.12025-01-31

What the citations cover

Citations by CMS category
  • Egress Deficiencies 8
  • Smoke Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 3
  • Other 4
Citations by CMS category
CategoryCitations
Egress Deficiencies8
Smoke Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies3
Construction Deficiencies2
Emergency Preparedness Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 22, 2026 — 8 citations

Citations issued on May 22, 2026
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (July 6, 2026)
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.No revisit needed (September 17, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 1, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 1, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 1, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 1, 2026)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (July 1, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 1, 2026)

January 31, 2025 — 14 citations

Citations issued on January 31, 2025
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (January 31, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (January 31, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (February 7, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (February 6, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (January 31, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 28, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 28, 2025)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (February 28, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (February 28, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (January 31, 2025)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (February 19, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (February 28, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 28, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (February 28, 2025)

November 8, 2023 — 6 citations

Citations issued on November 8, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (December 31, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 1, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 12, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 1, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 1, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (December 1, 2023)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.