Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

FOREST HILLS CENTER FOR REHABILITATION AND HEALING

NEWARK, NJ · 120 certified beds · Last Life Safety survey August 5, 2025

CMS Certification Number 315375 · first certified December 1997

Ownership

Operated by INFINITE CARE · For profit - Limited Liability company

  • Ownership changed May 1, 2022 (change of ownership)from FOREST HILL HEALTH CARE CENTER, INC.
30
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
15
Inspection & testing records
Of the citations on file

Position within NJ

30 citations — more than 94% of the 348 certified nursing homes in NJ. Compared within NJ rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 8. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 2 months from now. This facility’s last Life Safety survey was August 2025. Facilities in NJ are typically surveyed 16–20 months after the last one (median 17), measured over 431 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about FOREST HILLS CENTER FOR REHABILITATION AND HEALING

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

5 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 30 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NJ, and nationally. Surveyors differ markedly between states, so the NJ figure is the meaningful one.

This facility30NJ median15National median11
Citations on file over three years, compared
MeasureCitations
This facility30
Median facility in NJ15
Median facility nationally11

Survey history

Citations at each Life Safety survey
42021-07122023-12142025-08
Citations at each Life Safety survey
Survey dateCitations
July 27, 20214
December 12, 202312
August 5, 202514

Most-cited tags

Most-cited tags at this facility
K-05313K-03533K-03452K-09142K-07612K-03212K-09182K-03111
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0531Have elevators that firefighters can control in the event of a fire.32025-08-05
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-08-05
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-08-05
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22025-08-05
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22025-08-05
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22025-08-05
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-08-05
K-0311Have an enclosure around a vertical opening shaft.12023-12-12

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 4
  • Services Deficiencies 4
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies4
Services Deficiencies4
Miscellaneous Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 5, 2025 — 14 citations

Citations issued on August 5, 2025
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (September 30, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (October 22, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 22, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 22, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 22, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 22, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 22, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 22, 2025)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (October 23, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 22, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 22, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 22, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 22, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 22, 2025)

December 12, 2023 — 12 citations

Citations issued on December 12, 2023
TagWhat the surveyor checksStatus
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (January 26, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 26, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 26, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 26, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 26, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (February 9, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (January 26, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (January 26, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (January 26, 2024)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (January 26, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 26, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 26, 2024)

July 27, 2021 — 4 citations

Citations issued on July 27, 2021
TagWhat the surveyor checksStatus
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (September 27, 2021)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (September 27, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 27, 2021)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (September 27, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.