Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Fort Bayard Medical Center

Santa Clara, NM · 200 certified beds · Last Life Safety survey November 17, 2025

CMS Certification Number 325120 · first certified June 2009

Ownership

Independently operated (no chain recorded by CMS) · Government - State

No change of ownership on CMS record since January 1, 2016, when the records begin.

44
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
7
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within NM

44 citations — more than 100% of the 68 certified nursing homes in NM. Compared within NM rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 33 citations; the earlier surveys on file averaged 5.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2026 — about 1 month from now. This facility’s last Life Safety survey was November 2025. Facilities in NM are typically surveyed 13–15 months after the last one (median 15), measured over 55 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about Fort Bayard Medical Center

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

9 of the 44 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in NM, and nationally. Surveyors differ markedly between states, so the NM figure is the meaningful one.

This facility44NM median15National median11
Citations in CMS's current file, compared
MeasureCitations
This facility44
Median facility in NM15
Median facility nationally11

Survey history

Citations at each Life Safety survey
72023-0642024-08332025-11
Citations at each Life Safety survey
Survey dateCitations
June 1, 20237
August 9, 20244
November 17, 202533

Most-cited tags

Most-cited tags at this facility
K-07123K-03243K-03533K-09182K-03542E-00342E-00072E-00261
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32025-11-17
K-0324Provide properly protected cooking facilities.32025-11-17
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-11-17
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-11-17
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.22025-11-17
E-0034Provide a means of sharing information on occupancy/needs.22025-11-17
E-0007Address patient/client population and determine types of services needed.22025-11-17
E-0026Establish roles under a Waiver declared by secretary.12023-06-01

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Emergency Preparedness Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Miscellaneous Deficiencies 7
  • Other 6
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Emergency Preparedness Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies7
Miscellaneous Deficiencies7
Egress Deficiencies5
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 17, 2025 — 33 citations

Citations issued on November 17, 2025
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (May 25, 2026)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (May 25, 2026)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (May 25, 2026)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (May 25, 2026)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (May 25, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 11, 2026)
K-0100Meet other general requirements.Deficient, Provider has date of correction (May 25, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 25, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 25, 2026)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (May 25, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has plan of correction (September 15, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has plan of correction (September 15, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 25, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 25, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction (September 15, 2026)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (June 11, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has plan of correction (September 15, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (May 25, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (May 25, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 25, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 25, 2026)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has plan of correction (September 15, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 25, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 25, 2026)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (May 25, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (May 25, 2026)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (May 25, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (May 25, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has plan of correction (September 15, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has plan of correction (September 15, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 25, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (May 25, 2026)
K-0926Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.Deficient, Provider has date of correction (July 22, 2026)

August 9, 2024 — 4 citations

Citations issued on August 9, 2024
TagWhat the surveyor checksStatus
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 23, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 23, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 23, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 23, 2024)

June 1, 2023 — 7 citations

Citations issued on June 1, 2023
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (September 8, 2023)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (September 8, 2023)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (September 8, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 8, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 8, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 8, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 8, 2023)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.