Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

HIGHLAND MANOR OF ELKO REHABILITATION LLC

ELKO, NV · 146 certified beds · Last Life Safety survey August 7, 2025

CMS Certification Number 295078 · first certified February 2001

Ownership

Operated by THE CHARLY BELLO FAMILY, THE MAZE FAMILY, THE SWAIN FAMILY, & WALTER MYERS · For profit - Limited Liability company

  • Ownership changed April 18, 2024 (change of ownership)from DESERT HEALTH CARE FACILITIES INC
18
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within NV

18 citations — more than 20% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 6 citations; the earlier surveys in the window averaged 6. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (July 2026 to September 2026). Most NV facilities have been surveyed by October 2026. This facility’s last Life Safety survey was August 2025. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 117 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about HIGHLAND MANOR OF ELKO REHABILITATION LLC

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 18 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.

This facility18NV median26National median11
Citations on file over three years, compared
MeasureCitations
This facility18
Median facility in NV26
Median facility nationally11

Survey history

Citations at each Life Safety survey
42023-0582024-0762025-08
Citations at each Life Safety survey
Survey dateCitations
May 18, 20234
July 18, 20248
August 7, 20256

Most-cited tags

Most-cited tags at this facility
K-07123K-05113K-02222K-09202K-03532K-03741K-05211K-07411
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0712Have simulated fire drills held at unexpected times.32025-08-07
K-0511Have properly installed electrical wiring and gas equipment.32025-08-07
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-08-07
K-0920Ensure proper usage of power strips and extension cords.22024-07-18
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-08-07
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.12024-07-18
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.12024-07-18
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.12024-07-18

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Services Deficiencies 4
  • Miscellaneous Deficiencies 4
  • Smoke Deficiencies 3
  • Other 3
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies4
Services Deficiencies4
Miscellaneous Deficiencies4
Smoke Deficiencies3
Egress Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 7, 2025 — 6 citations

Citations issued on August 7, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 19, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (September 19, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 19, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 19, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 19, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (September 19, 2025)

July 18, 2024 — 8 citations

Citations issued on July 18, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (September 1, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 1, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 1, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 1, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (September 1, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (September 1, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 1, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 1, 2024)

May 18, 2023 — 4 citations

Citations issued on May 18, 2023
TagWhat the surveyor checksStatus
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 30, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 30, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 30, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (June 30, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.