Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
LIFE CARE CENTER OF SOUTH LAS VEGAS
LAS VEGAS, NV · 120 certified beds · Last Life Safety survey May 27, 2026
CMS Certification Number 295076 · first certified March 2000
Ownership
Operated by LIFE CARE CENTERS OF AMERICA · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within NV
69 citations — more than 100% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 26 citations; the earlier surveys on file averaged 14.3. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens May 2027 — about 6 months from now. This facility’s last Life Safety survey was May 2026. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 119 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured
Get an email about LIFE CARE CENTER OF SOUTH LAS VEGAS
One email when it happens. No account; stop it any time with one click.
8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
22 of the 69 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 69 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
How that compares
Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 69 |
| Median facility in NV | 26 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| February 23, 2024 | 2 |
| August 9, 2024 | 19 |
| June 13, 2025 | 22 |
| May 27, 2026 | 26 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2026-05-27 |
| E-0007 | Address patient/client population and determine types of services needed. | 3 | 2026-05-27 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 3 | 2026-05-27 |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | 3 | 2026-05-27 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3 | 2026-05-27 |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 3 | 2026-05-27 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2026-05-27 |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | 2 | 2026-05-27 |
What the citations cover
- Emergency Preparedness Deficiencies 22
- Smoke Deficiencies 21
- Miscellaneous Deficiencies 9
- Gas, Vacuum, and Electrical Systems Deficiencies 8
- Other 9
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 22 |
| Smoke Deficiencies | 21 |
| Miscellaneous Deficiencies | 9 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 8 |
| Egress Deficiencies | 5 |
| Services Deficiencies | 3 |
| Construction Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 27, 2026 — 26 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (July 20, 2026) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0025 | Create arrangements with other facilities to receive patients. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0031 | Provide emergency officials' contact information. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (July 20, 2026) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 20, 2026) |
| K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 24, 2026) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (July 17, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 24, 2026) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (July 17, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (July 17, 2026) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 17, 2026) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has date of correction (July 13, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 16, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (July 13, 2026) |
June 13, 2025 — 22 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0013 | Develop Emergency Preparedness policies and procedures. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (July 21, 2025) |
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0331 | Construct fire resistant interior walls. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0791 | Ensure that any exit in an area undergoing construction, repair, or improvements shall be inspected daily to ensure its ability to be used instantly in case of emergency. | Deficient, Provider has date of correction (July 21, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (July 21, 2025) |
August 9, 2024 — 19 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (October 4, 2024) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (October 4, 2024) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (October 4, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (October 4, 2024) |
| E-0029 | Develop a communication plan. | Deficient, Provider has date of correction (October 4, 2024) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (October 4, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0331 | Construct fire resistant interior walls. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0751 | Have restrictions on the use of flammable curtains. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0908 | Ensure gas and vacuum systems are inspected and tested as part of a maintenance program. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (October 4, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (October 4, 2024) |
February 23, 2024 — 2 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has no plan of correction |
| K-0700 | Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors. | Deficient, Provider has no plan of correction |
Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.