Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

LIFE CARE CENTER OF SOUTH LAS VEGAS

LAS VEGAS, NV · 120 certified beds · Last Life Safety survey May 27, 2026

CMS Certification Number 295076 · first certified March 2000

Ownership

Operated by LIFE CARE CENTERS OF AMERICA · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

69
Citations on file
CMS's current file
4
Life Safety surveys
CMS's current file
22
Tags cited more than once
Across separate surveys
24
Inspection & testing records
Of the citations on file

Position within NV

69 citations — more than 100% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 26 citations; the earlier surveys on file averaged 14.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens May 2027 — about 6 months from now. This facility’s last Life Safety survey was May 2026. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 119 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about LIFE CARE CENTER OF SOUTH LAS VEGAS

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

22 of the 69 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

1 physical-environment citation on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 69 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations in CMS's current file

Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.

This facility69NV median26National median11
Citations in CMS's current file, compared
MeasureCitations
This facility69
Median facility in NV26
Median facility nationally11

Survey history

Citations at each Life Safety survey
22024-02192024-08222025-06262026-05
Citations at each Life Safety survey
Survey dateCitations
February 23, 20242
August 9, 202419
June 13, 202522
May 27, 202626

Most-cited tags

Most-cited tags at this facility
K-03533E-00073K-02913K-03543K-07613K-03553K-09182K-03462
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-05-27
E-0007Address patient/client population and determine types of services needed.32026-05-27
K-0291Install emergency lighting that can last at least 1 1/2 hours.32026-05-27
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.32026-05-27
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32026-05-27
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.32026-05-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-05-27
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.22026-05-27

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 22
  • Smoke Deficiencies 21
  • Miscellaneous Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Other 9
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies22
Smoke Deficiencies21
Miscellaneous Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies5
Services Deficiencies3
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 27, 2026 — 26 citations

Citations issued on May 27, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (July 20, 2026)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (July 20, 2026)
E-0025Create arrangements with other facilities to receive patients.Deficient, Provider has date of correction (July 20, 2026)
E-0029Develop a communication plan.Deficient, Provider has date of correction (July 20, 2026)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (July 20, 2026)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (July 20, 2026)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (July 20, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (July 20, 2026)
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (July 13, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 13, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (July 13, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 13, 2026)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (July 13, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 24, 2026)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (July 17, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 24, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (July 17, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 13, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 13, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 17, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 16, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 17, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 16, 2026)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (July 13, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 16, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 13, 2026)

June 13, 2025 — 22 citations

Citations issued on June 13, 2025
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (July 21, 2025)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (July 21, 2025)
E-0013Develop Emergency Preparedness policies and procedures.Deficient, Provider has date of correction (July 21, 2025)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (July 21, 2025)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (July 21, 2025)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (July 21, 2025)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (July 21, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 21, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 21, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 21, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 21, 2025)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (July 21, 2025)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (July 21, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 21, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (July 21, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 21, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 21, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (July 21, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 21, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 21, 2025)
K-0791Ensure that any exit in an area undergoing construction, repair, or improvements shall be inspected daily to ensure its ability to be used instantly in case of emergency.Deficient, Provider has date of correction (July 21, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 21, 2025)

August 9, 2024 — 19 citations

Citations issued on August 9, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (October 4, 2024)
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (October 4, 2024)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (October 4, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 4, 2024)
E-0029Develop a communication plan.Deficient, Provider has date of correction (October 4, 2024)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (October 4, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 4, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 4, 2024)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (October 4, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 4, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 4, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 4, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 4, 2024)
K-0751Have restrictions on the use of flammable curtains.Deficient, Provider has date of correction (October 4, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 4, 2024)
K-0908Ensure gas and vacuum systems are inspected and tested as part of a maintenance program.Deficient, Provider has date of correction (October 4, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 4, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 4, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 4, 2024)

February 23, 2024 — 2 citations

Citations issued on February 23, 2024
TagWhat the surveyor checksStatus
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has no plan of correction
K-0700Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.Deficient, Provider has no plan of correction

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.