Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
MARQUIS CARE AT CENTENNIAL HILLS
LAS VEGAS, NV · 120 certified beds · Last Life Safety survey June 27, 2025
CMS Certification Number 295089 · first certified November 2010
Ownership
Operated by MARQUIS COMPANIES · For profit - Corporation
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within NV
37 citations — more than 80% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 9 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (June 2026 to July 2026), and past the point by which nine in ten NV facilities have been surveyed. This facility’s last Life Safety survey was June 2025. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 117 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about MARQUIS CARE AT CENTENNIAL HILLS
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
13 of the 37 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 37 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
How that compares
Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 37 |
| Median facility in NV | 26 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| July 27, 2023 | 16 |
| July 26, 2024 | 12 |
| June 27, 2025 | 9 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | 3 | 2025-06-27 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-06-27 |
| E-0015 | Address subsistence needs for staff and patients. | 3 | 2025-06-27 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-06-27 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 2 | 2024-07-26 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2024-07-26 |
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | 2 | 2024-07-26 |
| K-0511 | Have properly installed electrical wiring and gas equipment. | 2 | 2025-06-27 |
What the citations cover
- Emergency Preparedness Deficiencies 13
- Smoke Deficiencies 8
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Miscellaneous Deficiencies 5
- Other 5
| Category | Citations |
|---|---|
| Emergency Preparedness Deficiencies | 13 |
| Smoke Deficiencies | 8 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Miscellaneous Deficiencies | 5 |
| Egress Deficiencies | 3 |
| Services Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
June 27, 2025 — 9 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | No revisit needed (August 11, 2025) |
| E-0009 | Include a process for Emergency Preparedness collaboration. | No revisit needed (August 11, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | No revisit needed (August 11, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | No revisit needed (August 11, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | No revisit needed (August 11, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | No revisit needed (August 11, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | No revisit needed (August 11, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | No revisit needed (August 11, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | No revisit needed (August 11, 2025) |
July 26, 2024 — 12 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (August 15, 2024) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (August 15, 2024) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (August 15, 2024) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0791 | Ensure that any exit in an area undergoing construction, repair, or improvements shall be inspected daily to ensure its ability to be used instantly in case of emergency. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 15, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (August 15, 2024) |
July 27, 2023 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (September 10, 2023) |
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (September 10, 2023) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (September 10, 2023) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (September 10, 2023) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has date of correction (September 10, 2023) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0331 | Construct fire resistant interior walls. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0753 | Have restrictions on the use of highly flammable decorations. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0904 | Have a properly installed medical gas master alarm panel. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (September 10, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (September 10, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.