Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

SILVER HILLS HEALTH CARE CENTER

LAS VEGAS, NV · 155 certified beds · Last Life Safety survey August 20, 2025

CMS Certification Number 295066 · first certified October 1998

Ownership

Operated by COVENANT CARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

44
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within NV

44 citations — more than 94% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 16 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (July 2026 to September 2026). Most NV facilities have been surveyed by October 2026. This facility’s last Life Safety survey was August 2025. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 117 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about SILVER HILLS HEALTH CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

11 of the 44 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 44 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.

This facility44NV median26National median11
Citations on file over three years, compared
MeasureCitations
This facility44
Median facility in NV26
Median facility nationally11

Survey history

Citations at each Life Safety survey
122023-09162024-09162025-08
Citations at each Life Safety survey
Survey dateCitations
September 29, 202312
September 6, 202416
August 20, 202516

Most-cited tags

Most-cited tags at this facility
K-03533K-07613K-05113K-07413K-02912K-03452E-00392E-00152
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-08-20
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32025-08-20
K-0511Have properly installed electrical wiring and gas equipment.32025-08-20
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.32025-08-20
K-0291Install emergency lighting that can last at least 1 1/2 hours.22025-08-20
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-08-20
E-0039Conduct testing and exercise requirements.22025-08-20
E-0015Address subsistence needs for staff and patients.22024-09-06

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 11
  • Smoke Deficiencies 10
  • Miscellaneous Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Other 7
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies11
Smoke Deficiencies10
Miscellaneous Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies8
Services Deficiencies5
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 20, 2025 — 16 citations

Citations issued on August 20, 2025
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (October 3, 2025)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (October 3, 2025)
E-0029Develop a communication plan.Deficient, Provider has date of correction (October 3, 2025)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (October 3, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 3, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 15, 2025)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (September 12, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 12, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 12, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (October 4, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (September 12, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (September 12, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (September 12, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 12, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 12, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (September 12, 2025)

September 6, 2024 — 16 citations

Citations issued on September 6, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (October 21, 2024)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 21, 2024)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has date of correction (October 21, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 21, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 21, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 21, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 21, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 21, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 21, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 21, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 21, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (October 21, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 21, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 21, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (October 21, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 21, 2024)

September 29, 2023 — 12 citations

Citations issued on September 29, 2023
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (November 12, 2023)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (November 12, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (November 12, 2023)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (November 12, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 12, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (November 12, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (November 12, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 12, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 12, 2023)
K-0910Ensure when modifications are made that breach pipelines, testing is conducted on downstream portions of the piping system.Deficient, Provider has date of correction (November 12, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (November 12, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (November 12, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.