Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

TORREY PINES POST ACUTE AND REHABILITATION

LAS VEGAS, NV · 95 certified beds · Last Life Safety survey July 9, 2026

CMS Certification Number 295045 · first certified December 1988

Ownership

Operated by DAVID JOHNSON · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

42
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
13
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within NV

42 citations — more than 91% of the 66 certified nursing homes in NV. Compared within NV rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 24 citations; the earlier surveys on file averaged 9. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 7 months from now. This facility’s last Life Safety survey was July 2026. Facilities in NV are typically surveyed 11–13 months after the last one (median 12), measured over 119 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about TORREY PINES POST ACUTE AND REHABILITATION

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

10 of the 42 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 42 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations in CMS's current file

Compared with the median facility in NV, and nationally. Surveyors differ markedly between states, so the NV figure is the meaningful one.

This facility42NV median26National median11
Citations in CMS's current file, compared
MeasureCitations
This facility42
Median facility in NV26
Median facility nationally11

Survey history

Citations at each Life Safety survey
102024-0582025-06242026-07
Citations at each Life Safety survey
Survey dateCitations
May 10, 202410
June 27, 20258
July 9, 202624

Most-cited tags

Most-cited tags at this facility
K-05213K-05113K-09182E-00152K-03532K-02112K-07612K-07412
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.32026-07-09
K-0511Have properly installed electrical wiring and gas equipment.32026-07-09
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-07-09
E-0015Address subsistence needs for staff and patients.22026-07-09
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-07-09
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.22026-07-09
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22026-07-09
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22026-07-09

What the citations cover

Citations by CMS category
  • Emergency Preparedness Deficiencies 10
  • Smoke Deficiencies 9
  • Services Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 11
Citations by CMS category
CategoryCitations
Emergency Preparedness Deficiencies10
Smoke Deficiencies9
Services Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies6
Egress Deficiencies5

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

July 9, 2026 — 24 citations

Citations issued on July 9, 2026
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (August 31, 2026)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (August 31, 2026)
E-0032Provide primary/alternate means for communication.Deficient, Provider has date of correction (August 31, 2026)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (August 31, 2026)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (August 31, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 31, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 31, 2026)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 31, 2026)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (August 31, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 31, 2026)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 31, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 31, 2026)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (August 31, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 31, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 31, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 31, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 31, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 31, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 31, 2026)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (August 31, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 31, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 31, 2026)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (August 31, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 31, 2026)

June 27, 2025 — 8 citations

Citations issued on June 27, 2025
TagWhat the surveyor checksStatus
E-0015Address subsistence needs for staff and patients.No revisit needed (July 27, 2025)
E-0029Develop a communication plan.No revisit needed (July 27, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.No revisit needed (July 27, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.No revisit needed (July 27, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.No revisit needed (July 27, 2025)
K-0511Have properly installed electrical wiring and gas equipment.No revisit needed (July 27, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.No revisit needed (July 27, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.No revisit needed (July 27, 2025)

May 10, 2024 — 10 citations

Citations issued on May 10, 2024
TagWhat the surveyor checksStatus
E-0029Develop a communication plan.Deficient, Provider has date of correction (June 5, 2024)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (June 5, 2024)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (June 5, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 5, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 5, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (June 5, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (June 5, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 5, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 5, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (June 5, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.