Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Campbell Hall Rehabilitation Center Inc

Campbell Hall, NY · 134 certified beds · Last Life Safety survey December 22, 2024

CMS Certification Number 335657 · first certified September 1982

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

49
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
16
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within NY

49 citations — more than 99% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 15 citations; the earlier surveys in the window averaged 17. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: June 2026 to February 2027. This facility’s last Life Safety survey was December 2024. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Campbell Hall Rehabilitation Center Inc

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

6 of the 49 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 49 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility49NY median13National median11
Citations on file over three years, compared
MeasureCitations
This facility49
Median facility in NY13
Median facility nationally11

Survey history

Citations at each Life Safety survey
142021-06202022-04152024-12
Citations at each Life Safety survey
Survey dateCitations
June 24, 202114
April 29, 202220
December 22, 202415

Most-cited tags

Most-cited tags at this facility
K-09183K-02813K-03742K-03512E-00152K-02912K-07612K-01612
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.32024-12-22
K-0281Install proper backup exit lighting.32024-12-22
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.22024-12-22
K-0351Install an approved automatic sprinkler system.22022-04-29
E-0015Address subsistence needs for staff and patients.22024-12-22
K-0291Install emergency lighting that can last at least 1 1/2 hours.22022-04-29
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22022-04-29
K-0161Use approved construction type or materials.22024-12-22

What the citations cover

Citations by CMS category
  • Egress Deficiencies 11
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 9
  • Miscellaneous Deficiencies 6
  • Other 12
Citations by CMS category
CategoryCitations
Egress Deficiencies11
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies9
Miscellaneous Deficiencies6
Emergency Preparedness Deficiencies6
Electrical Deficiencies2
Services Deficiencies2
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

December 22, 2024 — 15 citations

Citations issued on December 22, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (January 10, 2025)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (January 15, 2025)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (January 28, 2025)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (December 29, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (January 9, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (January 23, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (January 23, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 28, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (January 27, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (December 20, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 9, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 21, 2025)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (January 10, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 27, 2025)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (January 13, 2025)

April 29, 2022 — 20 citations

Citations issued on April 29, 2022
TagWhat the surveyor checksStatus
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (June 18, 2022)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (June 18, 2022)
K-0161Use approved construction type or materials.Waiver has been granted (June 25, 2022)
K-0200Meet other general requirements.Deficient, Provider has date of correction (June 18, 2022)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (June 18, 2022)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (June 18, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 18, 2022)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 18, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 18, 2022)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 18, 2022)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Waiver has been granted (August 8, 2022)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 18, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 18, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (June 18, 2022)
K-0522Have an externally vented heating system.Deficient, Provider has date of correction (June 18, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 18, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 25, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 18, 2022)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 18, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 18, 2022)

June 24, 2021 — 14 citations

Citations issued on June 24, 2021
TagWhat the surveyor checksStatus
K-0224Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion.Deficient, Provider has date of correction (August 10, 2021)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (August 10, 2021)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (August 10, 2021)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 10, 2021)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 10, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 10, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 10, 2021)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 10, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 10, 2021)
K-0901Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.Deficient, Provider has date of correction (August 10, 2021)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 10, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 10, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 10, 2021)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (August 10, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.