Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

IDEAL SENIOR LIVING CENTER

ENDICOTT, NY · 150 certified beds · Last Life Safety survey February 23, 2026

CMS Certification Number 335520 · first certified May 1976

Also on this campus

The same campus holds a state-licensed assisted living facility, with its own state record on the Assisted Living Index: Ideal Senior Living Center (600 High Avenue). Matched by the telephone number the two records share. The records are separate and are never added together.

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

9
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
1
Tags cited more than once
Across separate surveys
2
Inspection & testing records
Of the citations on file

Position within NY

9 citations — more than 24% of the 592 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 4 citations; the earlier surveys on file averaged 2.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 9 months from now. This facility’s last Life Safety survey was February 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 21), measured over 520 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about IDEAL SENIOR LIVING CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

Physical environment (health survey)

2 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 9 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations in CMS's current file

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility9NY median14National median11
Citations in CMS's current file, compared
MeasureCitations
This facility9
Median facility in NY14
Median facility nationally11

Survey history

Citations at each Life Safety survey
22022-0232024-0442026-02
Citations at each Life Safety survey
Survey dateCitations
February 4, 20222
April 5, 20243
February 23, 20264

Most-cited tags

Most-cited tags at this facility
K-01332K-09151K-02221K-09201K-03721K-05311K-09211K-09181
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0133Install a two-hour-resistant firewall separation.22026-02-23
K-0915Have proper power supply for life support equipment.12026-02-23
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12024-04-05
K-0920Ensure proper usage of power strips and extension cords.12024-04-05
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12026-02-23
K-0531Have elevators that firefighters can control in the event of a fire.12026-02-23
K-0921Ensure that testing and maintenance of electrical equipment is performed.12022-02-04
K-0918Have generator or other power source capable of supplying service within 10 seconds.12022-02-04

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Construction Deficiencies 2
  • Services Deficiencies 1
  • Smoke Deficiencies 1
  • Other 1
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies4
Construction Deficiencies2
Services Deficiencies1
Smoke Deficiencies1
Egress Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 23, 2026 — 4 citations

Citations issued on February 23, 2026
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (April 20, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (April 20, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has plan of correction (February 5, 2027)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (April 20, 2026)

April 5, 2024 — 3 citations

Citations issued on April 5, 2024
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (May 8, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 8, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 8, 2024)

February 4, 2022 — 2 citations

Citations issued on February 4, 2022
TagWhat the surveyor checksStatus
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (March 15, 2022)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (March 10, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.