Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Hudson Valley Rehabilitation & Extended Care Ctr

Highland, NY · 203 certified beds · Last Life Safety survey February 27, 2026

CMS Certification Number 335399 · first certified August 1973

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

33
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
14
Inspection & testing records
Of the citations on file

Position within NY

33 citations — more than 94% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 18 citations; the earlier surveys in the window averaged 7.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens August 2027 — about 11 months from now. This facility’s last Life Safety survey was February 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Hudson Valley Rehabilitation & Extended Care Ctr

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 33 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility33NY median13National median11
Citations on file over three years, compared
MeasureCitations
This facility33
Median facility in NY13
Median facility nationally11

Survey history

Citations at each Life Safety survey
82019-0272023-01182026-02
Citations at each Life Safety survey
Survey dateCitations
February 27, 20198
January 26, 20237
February 27, 202618

Most-cited tags

Most-cited tags at this facility
K-02812K-02712K-09182K-03722K-03532K-03552K-03472K-03611
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0281Install proper backup exit lighting.22026-02-27
K-0271Have exits that are accessible at all times.22026-02-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-02-27
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-02-27
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-02-27
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22026-02-27
K-0347Properly provide smoke detection systems in areas open to corridors.22023-01-26
K-0361Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.12019-02-27

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 7
  • Services Deficiencies 2
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies7
Services Deficiencies2
Miscellaneous Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 27, 2026 — 18 citations

Citations issued on February 27, 2026
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (April 20, 2026)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (April 20, 2026)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (April 20, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 20, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 20, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 20, 2026)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 20, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 20, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (April 20, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (April 20, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 12, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (April 20, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 20, 2026)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (April 20, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 20, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (April 20, 2026)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (April 20, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (April 20, 2026)

January 26, 2023 — 7 citations

Citations issued on January 26, 2023
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 28, 2023)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (February 28, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (February 28, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (February 28, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 28, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (February 28, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 28, 2023)

February 27, 2019 — 8 citations

Citations issued on February 27, 2019
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 29, 2019)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (April 29, 2019)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (April 29, 2019)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (April 29, 2019)
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (April 29, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 29, 2019)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (April 29, 2019)
K-0361Ensure that waiting areas, nurse’s stations, gift shops, and cooking facilities, open to the corridor are properly protected.Deficient, Provider has date of correction (April 29, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.