Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
Onondaga Center for Rehabilitation and Nursing
MINOA, NY · 82 certified beds · Last Life Safety survey November 20, 2025
CMS Certification Number 335548 · first certified July 1973
Ownership
Operated by CENTERS HEALTH CARE · For profit - Corporation
- Ownership changed September 1, 2017 (change of ownership)from MINOA NURSING AND REHABILITATION CENTER LLC
Position within NY
39 citations — more than 97% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 10 citations; the earlier surveys in the window averaged 14.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens May 2027 — about 7 months from now. This facility’s last Life Safety survey was November 2025. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about Onondaga Center for Rehabilitation and Nursing
One email when it happens. No account; stop it any time with one click.
4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
6 of the 39 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 39 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0908 Keep all essential equipment working safely.
- F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 39 |
| Median facility in NY | 13 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| March 14, 2022 | 7 |
| May 10, 2024 | 22 |
| November 20, 2025 | 10 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0351 | Install an approved automatic sprinkler system. | 3 | 2025-11-20 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2025-11-20 |
| K-0281 | Install proper backup exit lighting. | 3 | 2025-11-20 |
| E-0037 | Establish staff and initial training requirements. | 2 | 2024-05-10 |
| E-0015 | Address subsistence needs for staff and patients. | 2 | 2025-11-20 |
| K-0923 | Have proper medical gas storage and administration areas. | 2 | 2025-11-20 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 2 | 2024-05-10 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 2 | 2024-05-10 |
What the citations cover
- Smoke Deficiencies 12
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Miscellaneous Deficiencies 6
- Emergency Preparedness Deficiencies 6
- Other 6
| Category | Citations |
|---|---|
| Smoke Deficiencies | 12 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Miscellaneous Deficiencies | 6 |
| Emergency Preparedness Deficiencies | 6 |
| Egress Deficiencies | 5 |
| Services Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
November 20, 2025 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (January 15, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (January 15, 2026) |
May 10, 2024 — 22 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (July 9, 2024) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (July 1, 2024) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Waiver has been granted (July 9, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (July 9, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 9, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (July 9, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 9, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (July 9, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (July 1, 2024) |
March 14, 2022 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (May 27, 2022) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (June 16, 2022) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (June 8, 2022) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (May 6, 2022) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (May 6, 2022) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 6, 2022) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (May 6, 2022) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.