Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Degraff Memorial Hospital-Skilled Nursing Facility

NORTH TONAWANDA, NY · 80 certified beds · Last Life Safety survey June 2, 2026

CMS Certification Number 335669 · first certified April 1984

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

13
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
1
Tags cited more than once
Across separate surveys
7
Inspection & testing records
Of the citations on file

Position within NY

13 citations — more than 44% of the 592 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 7 citations; the earlier surveys on file averaged 3. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2027 — about 12 months from now. This facility’s last Life Safety survey was June 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 21), measured over 520 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about Degraff Memorial Hospital-Skilled Nursing Facility

One email when it happens. No account; stop it any time with one click.

Which alerts

1 inspection-and-testing tag has been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 13 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations in CMS's current file

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility13NY median14National median11
Citations in CMS's current file, compared
MeasureCitations
This facility13
Median facility in NY14
Median facility nationally11

Survey history

Citations at each Life Safety survey
02023-0262024-1072026-06
Citations at each Life Safety survey
Survey dateCitations
February 22, 20230
October 3, 20246
June 2, 20267

Most-cited tags

Most-cited tags at this facility
K-03722K-02811K-03241K-07611K-09201K-05211K-09181K-09111
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22026-06-02
K-0281Install proper backup exit lighting.12024-10-03
K-0324Provide properly protected cooking facilities.12024-10-03
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.12026-06-02
K-0920Ensure proper usage of power strips and extension cords.12026-06-02
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.12026-06-02
K-0918Have generator or other power source capable of supplying service within 10 seconds.12024-10-03
K-0911Meet requirements for the installation and maintenance of electrical systems.12026-06-02

What the citations cover

Citations by CMS category
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Smoke Deficiencies 3
  • Egress Deficiencies 2
  • Construction Deficiencies 1
  • Other 2
Citations by CMS category
CategoryCitations
Gas, Vacuum, and Electrical Systems Deficiencies5
Smoke Deficiencies3
Egress Deficiencies2
Construction Deficiencies1
Miscellaneous Deficiencies1
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 2, 2026 — 7 citations

Citations issued on June 2, 2026
TagWhat the surveyor checksStatus
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (July 31, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 31, 2026)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 31, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 31, 2026)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (July 31, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 31, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 31, 2026)

October 3, 2024 — 6 citations

Citations issued on October 3, 2024
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (November 30, 2024)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (November 30, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 30, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 30, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (November 30, 2024)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.