Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

The Pearl Nursing Center of Rochester

Rochester, NY · 120 certified beds · Last Life Safety survey December 11, 2025

CMS Certification Number 335439 · first certified January 1975

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

53
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
19
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within NY

53 citations — more than 99% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 1 citation; the earlier surveys in the window averaged 17.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens June 2027 — about 8 months from now. This facility’s last Life Safety survey was December 2025. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about The Pearl Nursing Center of Rochester

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 53 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

12 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 53 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility53NY median13National median11
Citations on file over three years, compared
MeasureCitations
This facility53
Median facility in NY13
Median facility nationally11

Survey history

Citations at each Life Safety survey
52020-09242022-12232024-0612025-12
Citations at each Life Safety survey
Survey dateCitations
September 14, 20205
December 16, 202224
June 28, 202423
December 11, 20251

Most-cited tags

Most-cited tags at this facility
K-03213K-03243K-03632K-07122K-05112K-03532K-07612K-03452
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-06-28
K-0324Provide properly protected cooking facilities.32024-06-28
K-0363Install corridor and hallway doors that block smoke.22024-06-28
K-0712Have simulated fire drills held at unexpected times.22024-06-28
K-0511Have properly installed electrical wiring and gas equipment.22024-06-28
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-06-28
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.22024-06-28
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22024-06-28

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 20
  • Egress Deficiencies 9
  • Miscellaneous Deficiencies 8
  • Emergency Preparedness Deficiencies 7
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies20
Egress Deficiencies9
Miscellaneous Deficiencies8
Emergency Preparedness Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies5
Services Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

December 11, 2025 — 1 citation

Citations issued on December 11, 2025
TagWhat the surveyor checksStatus
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (February 16, 2026)

June 28, 2024 — 23 citations

Citations issued on June 28, 2024
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (August 26, 2024)
E-0029Develop a communication plan.Deficient, Provider has date of correction (August 26, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 26, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 26, 2024)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 26, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 26, 2024)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 26, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 26, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 26, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 3, 2024)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (August 20, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 27, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 26, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 26, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 26, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 26, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 26, 2024)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (August 26, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 26, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (August 26, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 27, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 27, 2024)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (September 27, 2024)

December 16, 2022 — 24 citations

Citations issued on December 16, 2022
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (February 21, 2023)
E-0029Develop a communication plan.Deficient, Provider has date of correction (February 21, 2023)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (February 21, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (February 21, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (February 21, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (February 21, 2023)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (February 21, 2023)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (February 21, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (February 21, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (February 21, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (February 21, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (February 21, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 21, 2023)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (February 21, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (February 21, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (February 21, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (February 21, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 21, 2023)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (February 21, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (February 21, 2023)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (February 21, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 21, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (February 21, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (February 21, 2023)

September 14, 2020 — 5 citations

Citations issued on September 14, 2020
TagWhat the surveyor checksStatus
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (November 2, 2020)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 2, 2020)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 2, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 2, 2020)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 2, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.