Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

BAPTIST HEALTH NURSING AND REHABILITATION CENTER

SCOTIA, NY · 262 certified beds · Last Life Safety survey June 15, 2026

CMS Certification Number 335612 · first certified November 1977

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

20
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
5
Tags cited more than once
Across separate surveys
11
Inspection & testing records
Of the citations on file

Position within NY

20 citations — more than 72% of the 592 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 12 citations; the earlier surveys on file averaged 4. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2027 — about 13 months from now. This facility’s last Life Safety survey was June 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 21), measured over 520 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about BAPTIST HEALTH NURSING AND REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 20 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations in CMS's current file

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility20NY median14National median11
Citations in CMS's current file, compared
MeasureCitations
This facility20
Median facility in NY14
Median facility nationally11

Survey history

Citations at each Life Safety survey
32021-0852023-10122026-06
Citations at each Life Safety survey
Survey dateCitations
August 10, 20213
October 24, 20235
June 15, 202612

Most-cited tags

Most-cited tags at this facility
K-03453K-03112K-09182K-05312K-03532K-03631K-03511K-02811
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32026-06-15
K-0311Have an enclosure around a vertical opening shaft.22026-06-15
K-0918Have generator or other power source capable of supplying service within 10 seconds.22026-06-15
K-0531Have elevators that firefighters can control in the event of a fire.22026-06-15
K-0353Inspect, test, and maintain automatic sprinkler systems.22026-06-15
K-0363Install corridor and hallway doors that block smoke.12026-06-15
K-0351Install an approved automatic sprinkler system.12021-08-10
K-0281Install proper backup exit lighting.12026-06-15

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 4
  • Services Deficiencies 3
  • Egress Deficiencies 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies4
Services Deficiencies3
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 15, 2026 — 12 citations

Citations issued on June 15, 2026
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has plan of correction (September 23, 2026)
K-0281Install proper backup exit lighting.Deficient, Provider has plan of correction (October 15, 2026)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has plan of correction (September 23, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has plan of correction (October 2, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has plan of correction (October 2, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has plan of correction (October 2, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has plan of correction (October 2, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has plan of correction (October 2, 2026)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has plan of correction (October 2, 2026)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has plan of correction (October 2, 2026)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has plan of correction (October 2, 2026)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has plan of correction (October 2, 2026)

October 24, 2023 — 5 citations

Citations issued on October 24, 2023
TagWhat the surveyor checksStatus
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (November 20, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (November 22, 2023)
K-0531Have elevators that firefighters can control in the event of a fire.Deficient, Provider has date of correction (November 24, 2023)
K-0907Ensure medical gas and vacuum systems have documented maintenance programs.Deficient, Provider has date of correction (November 28, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 7, 2023)

August 10, 2021 — 3 citations

Citations issued on August 10, 2021
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 13, 2021)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (September 3, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 17, 2021)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.