Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
The Grand Rehabilitation and Nursing at Barnwell
VALATIE, NY · 236 certified beds · Last Life Safety survey May 19, 2026
CMS Certification Number 335565 · first certified November 1976
Ownership
Operated by THE GRAND HEALTHCARE · For profit - Partnership
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within NY
51 citations — more than 99% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 23 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2027 — about 13 months from now. This facility’s last Life Safety survey was May 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about The Grand Rehabilitation and Nursing at Barnwell
One email when it happens. No account; stop it any time with one click.
6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
7 of the 51 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 51 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
How that compares
Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 51 |
| Median facility in NY | 13 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| June 28, 2024 | 11 |
| June 17, 2025 | 17 |
| May 19, 2026 | 23 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0511 | Have properly installed electrical wiring and gas equipment. | 3 | 2026-05-19 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-05-19 |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | 3 | 2026-05-19 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2026-05-19 |
| K-0281 | Install proper backup exit lighting. | 2 | 2026-05-19 |
| K-0271 | Have exits that are accessible at all times. | 2 | 2026-05-19 |
| K-0363 | Install corridor and hallway doors that block smoke. | 2 | 2026-05-19 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2026-05-19 |
What the citations cover
- Smoke Deficiencies 17
- Egress Deficiencies 10
- Gas, Vacuum, and Electrical Systems Deficiencies 9
- Services Deficiencies 7
- Other 8
| Category | Citations |
|---|---|
| Smoke Deficiencies | 17 |
| Egress Deficiencies | 10 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 9 |
| Services Deficiencies | 7 |
| Emergency Preparedness Deficiencies | 7 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 19, 2026 — 23 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has plan of correction (June 26, 2026) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0781 | Have restrictions on the use of portable space heaters. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0916 | Have a battery powered remote alarm panel in a location accessible by operating personnel. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has plan of correction (June 30, 2026) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has plan of correction (June 30, 2026) |
June 17, 2025 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has date of correction (August 12, 2025) |
| E-0007 | Address patient/client population and determine types of services needed. | Deficient, Provider has date of correction (August 12, 2025) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (August 12, 2025) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0915 | Have proper power supply for life support equipment. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 12, 2025) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (August 12, 2025) |
June 28, 2024 — 11 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0018 | Establish procedures for tracking staff and patients during an emergency. | Deficient, Provider has date of correction (August 27, 2024) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0341 | Install a fire alarm system that can be heard throughout the facility. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 20, 2024) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (September 9, 2024) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Waiver has been granted (September 9, 2024) |
| K-0531 | Have elevators that firefighters can control in the event of a fire. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 27, 2024) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (August 27, 2024) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.