Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Comprehensive Rehabilitation and Nursing Center at

WILLIAMSVILLE, NY · 142 certified beds · Last Life Safety survey February 5, 2026

CMS Certification Number 335172 · first certified January 1967

Ownership

Operated by EPHRAM LAHASKY · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

72
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
24
Tags cited more than once
Across separate surveys
22
Inspection & testing records
Of the citations on file

Position within NY

72 citations — more than 100% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 2 citations; the earlier surveys in the window averaged 23.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens July 2027 — about 10 months from now. This facility’s last Life Safety survey was February 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Comprehensive Rehabilitation and Nursing Center at

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

13 of the 72 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 72 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.

This facility72NY median13National median11
Citations on file over three years, compared
MeasureCitations
This facility72
Median facility in NY13
Median facility nationally11

Survey history

Citations at each Life Safety survey
172021-08312023-04222024-1222026-02
Citations at each Life Safety survey
Survey dateCitations
August 27, 202117
April 21, 202331
December 6, 202422
February 5, 20262

Most-cited tags

Most-cited tags at this facility
K-03253K-03213K-09183K-03243K-02113K-03533K-03633K-09233
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.32024-12-06
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-12-06
K-0918Have generator or other power source capable of supplying service within 10 seconds.32024-12-06
K-0324Provide properly protected cooking facilities.32024-12-06
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32026-02-05
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-12-06
K-0363Install corridor and hallway doors that block smoke.32024-12-06
K-0923Have proper medical gas storage and administration areas.32024-12-06

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 23
  • Egress Deficiencies 17
  • Emergency Preparedness Deficiencies 13
  • Gas, Vacuum, and Electrical Systems Deficiencies 12
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies23
Egress Deficiencies17
Emergency Preparedness Deficiencies13
Gas, Vacuum, and Electrical Systems Deficiencies12
Miscellaneous Deficiencies5
Construction Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 5, 2026 — 2 citations

Citations issued on February 5, 2026
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 6, 2026)
K-0300Meet other general requirements that are deficient.Deficient, Provider has date of correction (April 6, 2026)

December 6, 2024 — 22 citations

Citations issued on December 6, 2024
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (January 24, 2025)
E-0022Establish policies and procedures for sheltering.Deficient, Provider has date of correction (January 24, 2025)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (January 24, 2025)
E-0035Provide family notifications of emergency plan.Deficient, Provider has date of correction (January 24, 2025)
K-0200Meet other general requirements.Deficient, Provider has date of correction (January 31, 2025)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 24, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (January 31, 2025)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (January 31, 2025)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 31, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 31, 2025)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (January 31, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Waiver has been granted
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 31, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (January 31, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 31, 2025)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (January 31, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 31, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (January 31, 2025)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (February 1, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (February 20, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 31, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 31, 2025)

April 21, 2023 — 31 citations

Citations issued on April 21, 2023
TagWhat the surveyor checksStatus
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (June 20, 2023)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (June 20, 2023)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (June 20, 2023)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (June 20, 2023)
K-0100Meet other general requirements.Deficient, Provider has date of correction (June 20, 2023)
K-0200Meet other general requirements.Deficient, Provider has date of correction (August 4, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 20, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Waiver has been granted
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 20, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Waiver has been granted
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (June 20, 2023)
K-0281Install proper backup exit lighting.Deficient, Provider has date of correction (August 4, 2023)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 4, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Waiver has been granted
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 4, 2023)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (June 20, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted
K-0347Properly provide smoke detection systems in areas open to corridors.Deficient, Provider has date of correction (June 20, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (June 20, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 4, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (June 20, 2023)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (August 4, 2023)
K-0363Install corridor and hallway doors that block smoke.Waiver has been granted
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (June 20, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (June 20, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 20, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (August 4, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 4, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 4, 2023)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (August 4, 2023)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 4, 2023)

August 27, 2021 — 17 citations

Citations issued on August 27, 2021
TagWhat the surveyor checksStatus
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (October 7, 2021)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (October 7, 2021)
E-0024Establish policies and procedures for volunteers.Deficient, Provider has date of correction (October 7, 2021)
E-0026Establish roles under a Waiver declared by secretary.Deficient, Provider has date of correction (October 7, 2021)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 7, 2021)
K-0100Meet other general requirements.Deficient, Provider has date of correction (October 7, 2021)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 18, 2021)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (November 18, 2021)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (November 18, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (November 18, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 7, 2021)
K-0325Have properly installed hallway dispensers for alcohol-based hand rub.Deficient, Provider has date of correction (November 18, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 18, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 18, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 7, 2021)
K-0921Ensure that testing and maintenance of electrical equipment is performed.Deficient, Provider has date of correction (October 7, 2021)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (November 18, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.