Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
YONKERS GARDENS CENTER FOR NURSING AND REHAB
YONKERS, NY · 200 certified beds · Last Life Safety survey February 12, 2026
CMS Certification Number 335515 · first certified April 1976
Ownership
Operated by INFINITE CARE · For profit - Limited Liability company
- Ownership changed March 8, 2018 (change of ownership)to YONKERS GARDENS CENTER FOR REHABILITATION AND NURSING from ST JOSEPH'S HOSPITAL NURSING HOME OF YONKERS, NEW YORK, INC
Position within NY
37 citations — more than 97% of the 593 certified nursing homes in NY. Compared within NY rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 13 citations; the earlier surveys in the window averaged 12. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens August 2027 — about 10 months from now. This facility’s last Life Safety survey was February 2026. Facilities in NY are typically surveyed 18–25 months after the last one (median 22), measured over 523 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about YONKERS GARDENS CENTER FOR NURSING AND REHAB
One email when it happens. No account; stop it any time with one click.
5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
6 of the 37 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 37 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
How that compares
Compared with the median facility in NY, and nationally. Surveyors differ markedly between states, so the NY figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 37 |
| Median facility in NY | 13 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| May 22, 2019 | 17 |
| August 15, 2023 | 7 |
| February 12, 2026 | 13 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 3 | 2026-02-12 |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | 3 | 2026-02-12 |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | 3 | 2026-02-12 |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | 2 | 2026-02-12 |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | 2 | 2026-02-12 |
| E-0015 | Address subsistence needs for staff and patients. | 2 | 2023-08-15 |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | 2 | 2023-08-15 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2026-02-12 |
What the citations cover
- Smoke Deficiencies 9
- Egress Deficiencies 7
- Gas, Vacuum, and Electrical Systems Deficiencies 6
- Emergency Preparedness Deficiencies 6
- Other 9
| Category | Citations |
|---|---|
| Smoke Deficiencies | 9 |
| Egress Deficiencies | 7 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 6 |
| Emergency Preparedness Deficiencies | 6 |
| Miscellaneous Deficiencies | 5 |
| Electrical Deficiencies | 2 |
| Services Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
February 12, 2026 — 13 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0224 | Provide sliding doors free of hazards, operable without special knowledge or effort, and meet weight requirements to set door in motion. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0901 | Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel. | Deficient, Provider has date of correction (March 31, 2026) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (March 31, 2026) |
August 15, 2023 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (November 10, 2023) |
| E-0030 | List the names and contact information of those in the facility. | Deficient, Provider has date of correction (November 10, 2023) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (September 13, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (September 13, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (November 10, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (November 2, 2023) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (November 9, 2023) |
May 22, 2019 — 17 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0009 | Include a process for Emergency Preparedness collaboration. | Deficient, Provider has date of correction (July 16, 2019) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has date of correction (July 16, 2019) |
| E-0039 | Conduct testing and exercise requirements. | Deficient, Provider has date of correction (July 16, 2019) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0281 | Install proper backup exit lighting. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0901 | Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (July 16, 2019) |
| K-0921 | Ensure that testing and maintenance of electrical equipment is performed. | Deficient, Provider has date of correction (July 16, 2019) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.