Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

DELHI POST-ACUTE

CINCINNATI, OH · 116 certified beds · Last Life Safety survey May 23, 2024

CMS Certification Number 365530 · first certified April 1980

Ownership

Operated by PACS GROUP · For profit - Limited Liability company

  • Ownership changed September 1, 2019 (change of ownership)from PREMIER ESTATES 526 LLC
40
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within OH

40 citations — more than 96% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 15.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: January 2026 to January 2027. This facility’s last Life Safety survey was May 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about DELHI POST-ACUTE

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 40 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 40 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility40OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility40
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-02222021-0692024-05
Citations at each Life Safety survey
Survey dateCitations
February 28, 20199
June 28, 202122
May 23, 20249

Most-cited tags

Most-cited tags at this facility
K-07613K-03533K-07412K-03452E-00392K-07122K-09142K-07111
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32024-05-23
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-05-23
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-05-23
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22021-06-28
E-0039Conduct testing and exercise requirements.22021-06-28
K-0712Have simulated fire drills held at unexpected times.22021-06-28
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22021-06-28
K-0711Provide a written emergency evacuation plan.12019-02-28

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 13
  • Miscellaneous Deficiencies 9
  • Emergency Preparedness Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 7
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies13
Miscellaneous Deficiencies9
Emergency Preparedness Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies7
Services Deficiencies2
Egress Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 23, 2024 — 9 citations

Citations issued on May 23, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 12, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (July 12, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (July 12, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 12, 2024)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (July 12, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 12, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 12, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 12, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 12, 2024)

June 28, 2021 — 22 citations

Citations issued on June 28, 2021
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (September 17, 2021)
E-0030List the names and contact information of those in the facility.Deficient, Provider has date of correction (August 19, 2021)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (August 19, 2021)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (September 17, 2021)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (September 17, 2021)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (September 17, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 19, 2021)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (September 17, 2021)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (September 17, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 17, 2021)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 19, 2021)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 17, 2021)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (September 17, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 17, 2021)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 19, 2021)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 19, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (September 17, 2021)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 19, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (September 17, 2021)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 17, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 19, 2021)
K-0928Ensure equipment listed for use in oxygen-enriched atmospheres are correctly labeled.Deficient, Provider has date of correction (September 17, 2021)

February 28, 2019 — 9 citations

Citations issued on February 28, 2019
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 26, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 26, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 26, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 26, 2019)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (April 26, 2019)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 26, 2019)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 26, 2019)
K-0913Ensure operating rooms are properly protected and written records are maintained and available for inspection.Deficient, Provider has date of correction (April 26, 2019)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 26, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.