Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

MONTGOMERY CARE CENTER

CINCINNATI, OH · 99 certified beds · Last Life Safety survey December 19, 2024

CMS Certification Number 365327 · first certified July 1975

Ownership

Operated by CARECORE HEALTH · For profit - Limited Liability company

  • Ownership changed August 1, 2017 (change of ownership)from MONTGOMERY LONG TERM CARE, LLC
54
Citations on file
Rolling three-year window
5
Life Safety surveys
In the same window
15
Tags cited more than once
Across separate surveys
26
Inspection & testing records
Of the citations on file

Position within OH

54 citations — more than 100% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 12 citations; the earlier surveys in the window averaged 10.5. With 5 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: August 2026 to August 2027. This facility’s last Life Safety survey was December 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about MONTGOMERY CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

8 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

9 of the 54 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 54 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility54OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility54
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
132019-03212022-0362023-1222024-07122024-12
Citations at each Life Safety survey
Survey dateCitations
March 12, 201913
March 2, 202221
December 12, 20236
July 3, 20242
December 19, 202412

Most-cited tags

Most-cited tags at this facility
K-03454K-03534K-07124K-07613K-02913E-00392E-00372K-03462
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.42024-12-19
K-0353Inspect, test, and maintain automatic sprinkler systems.42024-12-19
K-0712Have simulated fire drills held at unexpected times.42024-12-19
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32024-12-19
K-0291Install emergency lighting that can last at least 1 1/2 hours.32024-12-19
E-0039Conduct testing and exercise requirements.22024-07-03
E-0037Establish staff and initial training requirements.22024-07-03
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.22023-12-12

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 19
  • Miscellaneous Deficiencies 9
  • Emergency Preparedness Deficiencies 9
  • Egress Deficiencies 8
  • Other 9
Citations by CMS category
CategoryCitations
Smoke Deficiencies19
Miscellaneous Deficiencies9
Emergency Preparedness Deficiencies9
Egress Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies6
Services Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

December 19, 2024 — 12 citations

Citations issued on December 19, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (January 31, 2025)
K-0232Have corridors or aisles that are unobstructed and are at least 8 feet in width.Deficient, Provider has date of correction (January 31, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (January 31, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 31, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 31, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 31, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 31, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (January 31, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (January 31, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (January 31, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (January 31, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 31, 2025)

July 3, 2024 — 2 citations

Citations issued on July 3, 2024
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (July 23, 2024)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (July 23, 2024)

December 12, 2023 — 6 citations

Citations issued on December 12, 2023
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 1, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 1, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (March 1, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 1, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (March 1, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (March 1, 2024)

March 2, 2022 — 21 citations

Citations issued on March 2, 2022
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (April 11, 2022)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (April 11, 2022)
E-0031Provide emergency officials' contact information.Deficient, Provider has date of correction (April 11, 2022)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (April 11, 2022)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (April 11, 2022)
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (April 11, 2022)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 11, 2022)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (April 11, 2022)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 11, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 11, 2022)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (April 11, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 11, 2022)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (April 11, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 11, 2022)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (April 11, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (April 11, 2022)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (April 11, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 11, 2022)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 11, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (April 11, 2022)
K-0928Ensure equipment listed for use in oxygen-enriched atmospheres are correctly labeled.Deficient, Provider has date of correction (April 11, 2022)

March 12, 2019 — 13 citations

Citations issued on March 12, 2019
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (May 16, 2019)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 16, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 16, 2019)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 16, 2019)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (May 16, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 16, 2019)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (May 16, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 16, 2019)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (May 16, 2019)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (May 16, 2019)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 16, 2019)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (May 16, 2019)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 16, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.