Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

NORWOOD TOWERS POST-ACUTE

CINCINNATI, OH · 120 certified beds · Last Life Safety survey February 11, 2026

CMS Certification Number 366238 · first certified April 2002

Ownership

Operated by PACS GROUP · For profit - Limited Liability company

  • Ownership changed September 1, 2019 (change of ownership)from PREMIER ESTATES 524 LLC
41
Citations on file
Rolling three-year window
4
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within OH

41 citations — more than 97% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 1 citation; the earlier surveys in the window averaged 13.3. With 4 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens October 2027 — about 12 months from now. This facility’s last Life Safety survey was February 2026. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about NORWOOD TOWERS POST-ACUTE

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 41 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility41OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility41
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
132021-05202024-0672025-1212026-02
Citations at each Life Safety survey
Survey dateCitations
May 27, 202113
June 27, 202420
December 16, 20257
February 11, 20261

Most-cited tags

Most-cited tags at this facility
K-07414K-03453K-05112K-03532K-03212K-02222K-05212K-03632
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.42026-02-11
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-12-16
K-0511Have properly installed electrical wiring and gas equipment.22024-06-27
K-0353Inspect, test, and maintain automatic sprinkler systems.22025-12-16
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-06-27
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22024-06-27
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.22024-06-27
K-0363Install corridor and hallway doors that block smoke.22024-06-27

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 17
  • Miscellaneous Deficiencies 10
  • Egress Deficiencies 5
  • Services Deficiencies 5
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies17
Miscellaneous Deficiencies10
Egress Deficiencies5
Services Deficiencies5
Gas, Vacuum, and Electrical Systems Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

February 11, 2026 — 1 citation

Citations issued on February 11, 2026
TagWhat the surveyor checksStatus
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 2, 2026)

December 16, 2025 — 7 citations

Citations issued on December 16, 2025
TagWhat the surveyor checksStatus
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (February 11, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (February 11, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (February 11, 2026)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has plan of correction (March 18, 2026)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (February 11, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (February 11, 2026)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 2, 2026)

June 27, 2024 — 20 citations

Citations issued on June 27, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 5, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 5, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (August 5, 2024)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 5, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 5, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 5, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 5, 2024)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (August 5, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 5, 2024)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (August 5, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 5, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 5, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 5, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 5, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 5, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 5, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 5, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (August 5, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (August 5, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 5, 2024)

May 27, 2021 — 13 citations

Citations issued on May 27, 2021
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 24, 2021)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 17, 2021)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 24, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 24, 2021)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 17, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 17, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 17, 2021)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 17, 2021)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 24, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 17, 2021)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 24, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 17, 2021)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 17, 2021)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.