Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PLEASANT RIDGE HEALTHCARE CENTER

CINCINNATI, OH · 99 certified beds · Last Life Safety survey May 30, 2025

CMS Certification Number 365196 · first certified October 1974

Ownership

Operated by COMMUNICARE HEALTH · For profit - Corporation

  • Ownership changed July 1, 2021 (change of ownership)from PLEASANT RIDGE CARE CENTER, INC.
36
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
11
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within OH

36 citations — more than 93% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 9 citations; the earlier surveys in the window averaged 13.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was May 2025. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PLEASANT RIDGE HEALTHCARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 36 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 36 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility36OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility36
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
92019-10182023-0892025-05
Citations at each Life Safety survey
Survey dateCitations
October 10, 20199
August 16, 202318
May 30, 20259

Most-cited tags

Most-cited tags at this facility
K-02713K-07122K-09142K-07412K-03512K-09182K-05112K-02222
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0271Have exits that are accessible at all times.32025-05-30
K-0712Have simulated fire drills held at unexpected times.22023-08-16
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22023-08-16
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22025-05-30
K-0351Install an approved automatic sprinkler system.22025-05-30
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-05-30
K-0511Have properly installed electrical wiring and gas equipment.22023-08-16
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22025-05-30

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Egress Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 5
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Egress Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies5
Services Deficiencies2
Emergency Preparedness Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 30, 2025 — 9 citations

Citations issued on May 30, 2025
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 25, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has plan of correction (February 17, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (January 29, 2026)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (July 25, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 25, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 25, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (July 25, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 25, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 25, 2025)

August 16, 2023 — 18 citations

Citations issued on August 16, 2023
TagWhat the surveyor checksStatus
E-0039Conduct testing and exercise requirements.Deficient, Provider has date of correction (October 16, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (October 16, 2023)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (October 16, 2023)
K-0271Have exits that are accessible at all times.Fire Safety Evaluation Survey (October 16, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (October 16, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 16, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 16, 2023)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (October 16, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 16, 2023)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (October 16, 2023)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 16, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 16, 2023)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (October 16, 2023)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 16, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (October 16, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (October 16, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (October 16, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 16, 2023)

October 10, 2019 — 9 citations

Citations issued on October 10, 2019
TagWhat the surveyor checksStatus
K-0271Have exits that are accessible at all times.Fire Safety Evaluation Survey (November 22, 2019)
K-0344Have an alternate power supply for its alarm system.Deficient, Provider has date of correction (January 3, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (January 3, 2020)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (January 3, 2020)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 3, 2020)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 3, 2020)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 3, 2020)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (January 3, 2020)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (January 3, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.