Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Heritage Healthcare of Euclid

EUCLID, OH · 75 certified beds · Last Life Safety survey June 28, 2024

CMS Certification Number 365730 · first certified April 1989

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

  • Ownership changed September 1, 2021 (change of ownership)to EMBASSY OF EUCLID from GATEWAY HEALTH CARE CENTRE LLC
38
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within OH

38 citations — more than 94% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 12. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window is open now: February 2026 to February 2027. This facility’s last Life Safety survey was June 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Heritage Healthcare of Euclid

One email when it happens. No account; stop it any time with one click.

Which alerts

6 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

7 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

7 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility38OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
162019-0682022-04142024-06
Citations at each Life Safety survey
Survey dateCitations
June 6, 201916
April 20, 20228
June 28, 202414

Most-cited tags

Most-cited tags at this facility
K-03213K-03533K-02223K-05112K-07412K-03722K-09182K-02712
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32024-06-28
K-0353Inspect, test, and maintain automatic sprinkler systems.32024-06-28
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.32024-06-28
K-0511Have properly installed electrical wiring and gas equipment.22024-06-28
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22024-06-28
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-06-28
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-06-28
K-0271Have exits that are accessible at all times.22022-04-20

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Emergency Preparedness Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Egress Deficiencies 5
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Emergency Preparedness Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies5
Egress Deficiencies5
Miscellaneous Deficiencies4
Services Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 28, 2024 — 14 citations

Citations issued on June 28, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 28, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 15, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 15, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 15, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 28, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 15, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 15, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 15, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 15, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 15, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 15, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 15, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 15, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 15, 2024)

April 20, 2022 — 8 citations

Citations issued on April 20, 2022
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (May 24, 2022)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (May 24, 2022)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 24, 2022)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (May 24, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 24, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 24, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 24, 2022)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 24, 2022)

June 6, 2019 — 16 citations

Citations issued on June 6, 2019
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (August 15, 2019)
E-0007Address patient/client population and determine types of services needed.Deficient, Provider has date of correction (August 15, 2019)
E-0009Include a process for Emergency Preparedness collaboration.Deficient, Provider has date of correction (August 15, 2019)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (August 15, 2019)
E-0018Establish procedures for tracking staff and patients during an emergency.Deficient, Provider has date of correction (August 15, 2019)
E-0034Provide a means of sharing information on occupancy/needs.Deficient, Provider has date of correction (August 15, 2019)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 15, 2019)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 15, 2019)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (August 15, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 15, 2019)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 15, 2019)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (August 15, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 15, 2019)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 15, 2019)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 15, 2019)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (August 15, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.