Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

VILLAGE AT ST EDWARD NRSG CARE

FAIRLAWN, OH · 81 certified beds · Last Life Safety survey March 2, 2026

CMS Certification Number 365836 · first certified July 1991

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

28
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
16
Inspection & testing records
Of the citations on file

Position within OH

28 citations — more than 83% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 12.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens October 2027 — about 13 months from now. This facility’s last Life Safety survey was March 2026. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about VILLAGE AT ST EDWARD NRSG CARE

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

3 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 28 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility28OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility28
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
162022-0992024-1232026-03
Citations at each Life Safety survey
Survey dateCitations
September 15, 202216
December 12, 20249
March 2, 20263

Most-cited tags

Most-cited tags at this facility
K-09182K-05112K-02232K-03532K-09232K-02221K-03621K-05001
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-12-12
K-0511Have properly installed electrical wiring and gas equipment.22024-12-12
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.22026-03-02
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-12-12
K-0923Have proper medical gas storage and administration areas.22026-03-02
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.12024-12-12
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.12022-09-15
K-0500Meet other general requirements that are deficient.12026-03-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Egress Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Services Deficiencies 4
  • Other 2
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Egress Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies5
Services Deficiencies4
Miscellaneous Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 2, 2026 — 3 citations

Citations issued on March 2, 2026
TagWhat the surveyor checksStatus
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (March 27, 2026)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (March 27, 2026)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (March 27, 2026)

December 12, 2024 — 9 citations

Citations issued on December 12, 2024
TagWhat the surveyor checksStatus
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (December 27, 2024)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Waiver has been granted (March 6, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (December 27, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 27, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (December 27, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (December 27, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 27, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (December 27, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (December 27, 2024)

September 15, 2022 — 16 citations

Citations issued on September 15, 2022
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (October 15, 2022)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (October 15, 2022)
K-0252Provide at least two remote exits on each floor or fire section of the building.Deficient, Provider has date of correction (October 15, 2022)
K-0311Have an enclosure around a vertical opening shaft.Waiver has been granted (January 30, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 15, 2022)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (October 15, 2022)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 15, 2022)
K-0351Install an approved automatic sprinkler system.Deficient, Provider has date of correction (October 15, 2022)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 15, 2022)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (October 15, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 15, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 15, 2022)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (October 15, 2022)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (October 15, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 15, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (October 15, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.