Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

KIRTLAND WOODS OF JOURNEY

KIRTLAND, OH · 177 certified beds · Last Life Safety survey May 5, 2026

CMS Certification Number 365290 · first certified June 1973

Ownership

Operated by JOURNEY HEALTHCARE · For profit - Limited Liability company

  • New ownershipOwnership changed October 1, 2024 (change of ownership)from KIRTLAND REHAB AND CARE, LLC
46
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
13
Tags cited more than once
Across separate surveys
23
Inspection & testing records
Of the citations on file

Position within OH

46 citations — more than 98% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 7 citations; the earlier surveys in the window averaged 19.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens December 2027 — about 15 months from now. This facility’s last Life Safety survey was May 2026. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about KIRTLAND WOODS OF JOURNEY

One email when it happens. No account; stop it any time with one click.

Which alerts

9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

1 of the 46 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

16 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 46 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0908 Keep all essential equipment working safely.
  • F-0924 Put firmly secured handrails on each side of hallways.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility46OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility46
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
172023-07222024-0572026-05
Citations at each Life Safety survey
Survey dateCitations
July 20, 202317
May 2, 202422
May 5, 20267

Most-cited tags

Most-cited tags at this facility
K-02113K-02913K-07613K-03213K-07122K-05002K-03532K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32026-05-05
K-0291Install emergency lighting that can last at least 1 1/2 hours.32026-05-05
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.32026-05-05
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.32026-05-05
K-0712Have simulated fire drills held at unexpected times.22024-05-02
K-0500Meet other general requirements that are deficient.22026-05-05
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-05-02
K-0324Provide properly protected cooking facilities.22024-05-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Egress Deficiencies 10
  • Miscellaneous Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Egress Deficiencies10
Miscellaneous Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies6
Services Deficiencies5
Emergency Preparedness Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 5, 2026 — 7 citations

Citations issued on May 5, 2026
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (June 3, 2026)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (June 3, 2026)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has date of correction (June 3, 2026)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (June 3, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (June 3, 2026)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 3, 2026)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (June 3, 2026)

May 2, 2024 — 22 citations

Citations issued on May 2, 2024
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (August 21, 2024)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (July 18, 2024)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (August 21, 2024)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (July 18, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 18, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (August 21, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (July 18, 2024)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (July 18, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 21, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (July 18, 2024)
K-0363Install corridor and hallway doors that block smoke.Waiver has been granted (July 18, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 21, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (July 18, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 21, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 21, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (July 18, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (July 18, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 21, 2024)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (July 18, 2024)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (August 21, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 18, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 18, 2024)

July 20, 2023 — 17 citations

Citations issued on July 20, 2023
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (November 14, 2023)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (November 14, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (November 14, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (December 6, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (December 6, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (November 14, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (December 6, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (December 6, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (December 6, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (December 6, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (December 6, 2023)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 14, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (November 14, 2023)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (November 14, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 14, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 14, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (November 14, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.