Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
GARDENS OF NORTH OLMSTED
NORTH OLMSTED, OH · 99 certified beds · Last Life Safety survey July 29, 2024
CMS Certification Number 365310 · first certified July 1974
Ownership
Independently operated (no chain recorded by CMS) · For profit - Partnership
- Ownership changed December 31, 2021 (change of ownership)from NORTH OLMSTED HEALTHCARE LLC
Position within OH
58 citations — more than 100% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 1 citation; the earlier surveys in the window averaged 19. With 4 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window is open now: March 2026 to March 2027. This facility’s last Life Safety survey was July 2024. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about GARDENS OF NORTH OLMSTED
One email when it happens. No account; stop it any time with one click.
9 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
7 of the 58 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
11 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 58 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0880 Provide and implement an infection prevention and control program.
- F-0926 Have policies on smoking.
How that compares
Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 58 |
| Median facility in OH | 16 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| August 2, 2018 | 15 |
| September 26, 2019 | 22 |
| December 14, 2022 | 20 |
| July 29, 2024 | 1 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | 4 | 2024-07-29 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 3 | 2022-12-14 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 3 | 2022-12-14 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 3 | 2022-12-14 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2022-12-14 |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | 2 | 2022-12-14 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | 2 | 2019-09-26 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 2 | 2022-12-14 |
What the citations cover
- Smoke Deficiencies 20
- Gas, Vacuum, and Electrical Systems Deficiencies 10
- Egress Deficiencies 8
- Miscellaneous Deficiencies 7
- Other 13
| Category | Citations |
|---|---|
| Smoke Deficiencies | 20 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 10 |
| Egress Deficiencies | 8 |
| Miscellaneous Deficiencies | 7 |
| Emergency Preparedness Deficiencies | 7 |
| Services Deficiencies | 4 |
| Construction Deficiencies | 2 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
July 29, 2024 — 1 citation
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 31, 2024) |
December 14, 2022 — 20 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0004 | Develop and maintain an Emergency Preparedness Program (EP). | Deficient, Provider has date of correction (January 31, 2023) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0346 | Follow proper procedures when the fire alarm was out of service for more than 4 hours. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0711 | Provide a written emergency evacuation plan. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0761 | To conduct inspection, testing and maintenance of fire doors by qualified individuals. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (January 31, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (January 31, 2023) |
September 26, 2019 — 22 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0034 | Provide a means of sharing information on occupancy/needs. | Deficient, Provider has plan of correction (December 26, 2019) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has plan of correction (December 26, 2019) |
| E-0037 | Establish staff and initial training requirements. | Deficient, Provider has plan of correction (December 26, 2019) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (December 26, 2019) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0321 | Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0325 | Have properly installed hallway dispensers for alcohol-based hand rub. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0351 | Install an approved automatic sprinkler system. | Deficient, Provider has date of correction (December 26, 2019) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0511 | Have properly installed electrical wiring and gas equipment. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0541 | Install properly constructed and protected linen or trash chutes. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (December 23, 2019) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (December 23, 2019) |
August 2, 2018 — 15 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0022 | Establish policies and procedures for sheltering. | Deficient, Provider has date of correction (September 18, 2018) |
| E-0024 | Establish policies and procedures for volunteers. | Deficient, Provider has date of correction (September 18, 2018) |
| E-0026 | Establish roles under a Waiver declared by secretary. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0352 | Properly install and monitor supervisory attachments on automatic sprinkler systems. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0354 | Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (September 18, 2018) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (September 18, 2018) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.