Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

HERITAGE HEALTH CARE CENTER

OAKWOOD VILLAGE, OH · 60 certified beds · Last Life Safety survey November 27, 2023

CMS Certification Number 365401 · first certified December 1978

Ownership

Operated by EMBASSY HEALTHCARE · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

38
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
18
Inspection & testing records
Of the citations on file

Position within OH

38 citations — more than 94% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 14. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Past the typical window (July 2025 to July 2026). Most OH facilities have been surveyed by November 2026. This facility’s last Life Safety survey was November 2023. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about HERITAGE HEALTH CARE CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 38 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 38 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility38OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility38
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
132019-03152021-07102023-11
Citations at each Life Safety survey
Survey dateCitations
March 28, 201913
July 27, 202115
November 27, 202310

Most-cited tags

Most-cited tags at this facility
K-03453K-09232E-00372K-03632K-09142K-09182K-03312K-07122
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32023-11-27
K-0923Have proper medical gas storage and administration areas.22023-11-27
E-0037Establish staff and initial training requirements.22021-07-27
K-0363Install corridor and hallway doors that block smoke.22021-07-27
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22023-11-27
K-0918Have generator or other power source capable of supplying service within 10 seconds.22021-07-27
K-0331Construct fire resistant interior walls.22021-07-27
K-0712Have simulated fire drills held at unexpected times.22023-11-27

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 14
  • Miscellaneous Deficiencies 9
  • Gas, Vacuum, and Electrical Systems Deficiencies 8
  • Egress Deficiencies 3
  • Other 4
Citations by CMS category
CategoryCitations
Smoke Deficiencies14
Miscellaneous Deficiencies9
Gas, Vacuum, and Electrical Systems Deficiencies8
Egress Deficiencies3
Emergency Preparedness Deficiencies2
Services Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

November 27, 2023 — 10 citations

Citations issued on November 27, 2023
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (January 1, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (June 20, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (January 1, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (January 1, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (January 1, 2024)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (January 1, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (January 1, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (January 1, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (January 1, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (January 1, 2024)

July 27, 2021 — 15 citations

Citations issued on July 27, 2021
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (August 24, 2021)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 24, 2021)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 24, 2021)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 24, 2021)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (August 24, 2021)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 24, 2021)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 24, 2021)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 24, 2021)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 24, 2021)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 24, 2021)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 24, 2021)
K-0751Have restrictions on the use of flammable curtains.Deficient, Provider has date of correction (August 24, 2021)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 24, 2021)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 24, 2021)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (August 24, 2021)

March 28, 2019 — 13 citations

Citations issued on March 28, 2019
TagWhat the surveyor checksStatus
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (July 3, 2019)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 3, 2019)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 3, 2019)
K-0331Construct fire resistant interior walls.Deficient, Provider has date of correction (July 3, 2019)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (July 3, 2019)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (July 3, 2019)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (July 3, 2019)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (July 3, 2019)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (July 3, 2019)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 3, 2019)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 16, 2019)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 16, 2019)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (July 3, 2019)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.