Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

ARBORS AT OREGON

OREGON, OH · 87 certified beds · Last Life Safety survey June 25, 2026

CMS Certification Number 365523 · first certified April 1980

Ownership

Operated by ARBORS AT OHIO · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

21
Citations on file
CMS's current file
3
Life Safety surveys
CMS's current file
5
Tags cited more than once
Across separate surveys
13
Inspection & testing records
Of the citations on file

Position within OH

21 citations — more than 67% of the 924 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in CMS's current file.

The latest survey found 2 citations; the earlier surveys on file averaged 9.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2028 — about 15 months from now. This facility’s last Life Safety survey was June 2026. Facilities in OH are typically surveyed 19–32 months after the last one (median 26), measured over 985 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured

Get an email about ARBORS AT OREGON

One email when it happens. No account; stop it any time with one click.

Which alerts

4 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 21 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations in CMS's current file

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility21OH median16National median11
Citations in CMS's current file, compared
MeasureCitations
This facility21
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
72022-10122024-0822026-06
Citations at each Life Safety survey
Survey dateCitations
October 6, 20227
August 5, 202412
June 25, 20262

Most-cited tags

Most-cited tags at this facility
K-03723K-07122K-09182K-03532K-09142K-02911K-09151K-03741
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.32026-06-25
K-0712Have simulated fire drills held at unexpected times.22024-08-05
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-08-05
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-08-05
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.22024-08-05
K-0291Install emergency lighting that can last at least 1 1/2 hours.12024-08-05
K-0915Have proper power supply for life support equipment.12024-08-05
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.12024-08-05

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Miscellaneous Deficiencies 4
  • Egress Deficiencies 2
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies6
Miscellaneous Deficiencies4
Egress Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 25, 2026 — 2 citations

Citations issued on June 25, 2026
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (July 14, 2026)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (July 14, 2026)

August 5, 2024 — 12 citations

Citations issued on August 5, 2024
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 30, 2024)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 30, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 30, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (August 30, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Waiver has been granted (December 1, 2024)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (August 30, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 30, 2024)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (August 30, 2024)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 30, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 30, 2024)
K-0915Have proper power supply for life support equipment.Deficient, Provider has date of correction (August 30, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 30, 2024)

October 6, 2022 — 7 citations

Citations issued on October 6, 2022
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (November 2, 2022)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (November 2, 2022)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (November 2, 2022)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (November 2, 2022)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (November 2, 2022)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (November 2, 2022)
K-0922Meet requirements for the use and maintenance of medical gas equipment.Deficient, Provider has date of correction (November 2, 2022)

Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.