Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

PARK TERRACE REHABILITATION CENTER

TOLEDO, OH · 99 certified beds · Last Life Safety survey March 20, 2025

CMS Certification Number 365339 · first certified November 1976

Ownership

Independently operated (no chain recorded by CMS) · For profit - Limited Liability company

  • Ownership changed June 27, 2024 (change of ownership)from PARK TERRACE NURSING LLC
43
Citations on file
Rolling three-year window
5
Life Safety surveys
In the same window
10
Tags cited more than once
Across separate surveys
17
Inspection & testing records
Of the citations on file

Position within OH

43 citations — more than 98% of the 922 certified nursing homes in OH. Compared within OH rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 23 citations; the earlier surveys in the window averaged 10.8. With 5 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens November 2026 — about 1 month from now. This facility’s last Life Safety survey was March 2025. Facilities in OH are typically surveyed 20–32 months after the last one (median 26), measured over 889 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about PARK TERRACE REHABILITATION CENTER

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

5 of the 43 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

13 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 43 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0921 Make sure that the nursing home area is safe, easy to use, clean and comfortable for residents, staff and the public.

How that compares

Citations on file over three years

Compared with the median facility in OH, and nationally. Surveyors differ markedly between states, so the OH figure is the meaningful one.

This facility43OH median16National median11
Citations on file over three years, compared
MeasureCitations
This facility43
Median facility in OH16
Median facility nationally11

Survey history

Citations at each Life Safety survey
82020-02112023-0112023-11232025-03232025-03
Citations at each Life Safety survey
Survey dateCitations
February 6, 20208
January 13, 202311
November 30, 20231
March 20, 202523
March 20, 202523

Most-cited tags

Most-cited tags at this facility
K-02113K-03533K-09203K-03633K-03453K-07532K-02222K-03242
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.32025-03-20
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-03-20
K-0920Ensure proper usage of power strips and extension cords.32025-03-20
K-0363Install corridor and hallway doors that block smoke.32025-03-20
K-0345Have approved installation, maintenance and testing program for fire alarm systems.32025-03-20
K-0753Have restrictions on the use of highly flammable decorations.22025-03-20
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.22023-01-13
K-0324Provide properly protected cooking facilities.22025-03-20

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 16
  • Egress Deficiencies 7
  • Miscellaneous Deficiencies 7
  • Gas, Vacuum, and Electrical Systems Deficiencies 6
  • Other 7
Citations by CMS category
CategoryCitations
Smoke Deficiencies16
Egress Deficiencies7
Miscellaneous Deficiencies7
Gas, Vacuum, and Electrical Systems Deficiencies6
Emergency Preparedness Deficiencies5
Services Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 20, 2025 — 23 citations

Citations issued on March 20, 2025
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (May 13, 2025)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has date of correction (May 13, 2025)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (May 13, 2025)
E-0037Establish staff and initial training requirements.Deficient, Provider has date of correction (May 13, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (May 13, 2025)
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (May 13, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (May 13, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (May 13, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (May 13, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Waiver has been granted (May 8, 2025)
K-0346Follow proper procedures when the fire alarm was out of service for more than 4 hours.Deficient, Provider has date of correction (May 13, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 13, 2025)
K-0354Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.Deficient, Provider has date of correction (May 13, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 13, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 13, 2025)
K-0511Have properly installed electrical wiring and gas equipment.Deficient, Provider has date of correction (May 13, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (May 13, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 13, 2025)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (May 13, 2025)
K-0781Have restrictions on the use of portable space heaters.Deficient, Provider has date of correction (May 13, 2025)
K-0915Have proper power supply for life support equipment.Waiver has been granted (May 8, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (May 13, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (May 13, 2025)

November 30, 2023 — 1 citation

Citations issued on November 30, 2023
TagWhat the surveyor checksStatus
K-0351Install an approved automatic sprinkler system.Waiver has been granted (March 25, 2024)

January 13, 2023 — 11 citations

Citations issued on January 13, 2023
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 16, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 16, 2023)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (March 16, 2023)
K-0341Install a fire alarm system that can be heard throughout the facility.Deficient, Provider has date of correction (March 16, 2023)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 16, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 16, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 16, 2023)
K-0711Provide a written emergency evacuation plan.Deficient, Provider has date of correction (March 16, 2023)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (March 16, 2023)
K-0753Have restrictions on the use of highly flammable decorations.Deficient, Provider has date of correction (March 16, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 16, 2023)

February 6, 2020 — 8 citations

Citations issued on February 6, 2020
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (March 11, 2020)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (March 11, 2020)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 11, 2020)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (March 11, 2020)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 11, 2020)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (March 11, 2020)
K-0916Have a battery powered remote alarm panel in a location accessible by operating personnel.Deficient, Provider has date of correction (March 11, 2020)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (March 11, 2020)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.