Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Tulsa Center for Rehabilitation and Healthcare

TULSA, OK · 180 certified beds · Last Life Safety survey March 20, 2024

CMS Certification Number 375568 · first certified October 2016

Ownership

Independently operated (no chain recorded by CMS) · For profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

11
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
2
Tags cited more than once
Across separate surveys
6
Inspection & testing records
Of the citations on file

Position within OK

11 citations — more than 70% of the 283 certified nursing homes in OK. Compared within OK rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 3 citations; the earlier surveys in the window averaged 4. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (May 2025 to July 2025), and past the point by which nine in ten OK facilities have been surveyed. This facility’s last Life Safety survey was March 2024. Facilities in OK are typically surveyed 14–16 months after the last one (median 15), measured over 277 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Tulsa Center for Rehabilitation and Healthcare

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 11 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0919 Make sure that a working call system is available in each resident's bathroom and bathing area.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in OK, and nationally. Surveyors differ markedly between states, so the OK figure is the meaningful one.

This facility11OK median8National median11
Citations on file over three years, compared
MeasureCitations
This facility11
Median facility in OK8
Median facility nationally11

Survey history

Citations at each Life Safety survey
42022-0242023-0932024-03
Citations at each Life Safety survey
Survey dateCitations
February 22, 20224
September 13, 20234
March 20, 20243

Most-cited tags

Most-cited tags at this facility
K-02912K-03722K-03621K-03211K-03741K-09231K-07411K-09121
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0291Install emergency lighting that can last at least 1 1/2 hours.22023-09-13
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-03-20
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.12022-02-22
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.12024-03-20
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.12022-02-22
K-0923Have proper medical gas storage and administration areas.12022-02-22
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.12024-03-20
K-0912Have power receptacles that are properly grounded.12023-09-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 6
  • Gas, Vacuum, and Electrical Systems Deficiencies 2
  • Egress Deficiencies 2
  • Miscellaneous Deficiencies 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies6
Gas, Vacuum, and Electrical Systems Deficiencies2
Egress Deficiencies2
Miscellaneous Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 20, 2024 — 3 citations

Citations issued on March 20, 2024
TagWhat the surveyor checksStatus
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 10, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (May 10, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (May 10, 2024)

September 13, 2023 — 4 citations

Citations issued on September 13, 2023
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (March 15, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (March 15, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (March 15, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (March 15, 2024)

February 22, 2022 — 4 citations

Citations issued on February 22, 2022
TagWhat the surveyor checksStatus
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (April 30, 2022)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (April 30, 2022)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (May 4, 2022)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (May 4, 2022)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.