Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
LAUREL HILL NURSING CENTER
GRANTS PASS, OR · 44 certified beds · Last Life Safety survey July 24, 2026
CMS Certification Number 385232 · first certified October 1992
Ownership
Operated by REGENCY PACIFIC MANAGEMENT · For profit - Individual
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within OR
13 citations — more than 59% of the 128 certified nursing homes in OR. Compared within OR rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 0 citations; the earlier surveys on file averaged 6.5. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
The window opens November 2027 — about 12 months from now. This facility’s last Life Safety survey was July 2026. Facilities in OR are typically surveyed 15–17 months after the last one (median 16), measured over 188 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to about three years in Virginia. How the window is measured
Get an email about LAUREL HILL NURSING CENTER
One email when it happens. No account; stop it any time with one click.
2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities cited for sprinkler inspection and testing in CMS’s current file are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
1 of the 13 citations on file is Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 13 Life Safety citations above. The Physical Environment Index
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
How that compares
Compared with the median facility in OR, and nationally. Surveyors differ markedly between states, so the OR figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 13 |
| Median facility in OR | 11 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| December 15, 2023 | 6 |
| March 28, 2025 | 7 |
| July 24, 2026 | 0 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | 2 | 2025-03-28 |
| K-0500 | Meet other general requirements that are deficient. | 2 | 2025-03-28 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 2 | 2025-03-28 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 1 | 2025-03-28 |
| E-0020 | Establish policies and procedures including evacuation. | 1 | 2025-03-28 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 1 | 2023-12-15 |
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | 1 | 2023-12-15 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | 1 | 2025-03-28 |
What the citations cover
- Smoke Deficiencies 5
- Gas, Vacuum, and Electrical Systems Deficiencies 3
- Services Deficiencies 2
- Egress Deficiencies 1
- Other 2
| Category | Citations |
|---|---|
| Smoke Deficiencies | 5 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 3 |
| Services Deficiencies | 2 |
| Egress Deficiencies | 1 |
| Emergency Preparedness Deficiencies | 1 |
| Miscellaneous Deficiencies | 1 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
March 28, 2025 — 7 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (May 8, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (May 8, 2025) |
December 15, 2023 — 6 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0211 | Keep aisles, corridors, and exits free of obstruction in case of emergency. | Deficient, Provider has date of correction (January 18, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (January 18, 2024) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (January 18, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (January 18, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (January 18, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (January 18, 2024) |
Reflects the CMS posting of October 1, 2026. Surveys conducted in the last few months may not appear yet.