Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record
KADIMA REHABILITATION & NURSING AT HARMONY
HARMONY, PA · 115 certified beds · Last Life Safety survey May 9, 2025
CMS Certification Number 395758 · first certified June 1988
Ownership
Operated by KADIMA HEALTHCARE GROUP · For profit - Limited Liability company
No change of ownership on CMS record since January 1, 2016, when the records begin.
Position within PA
55 citations — more than 100% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated
The latest survey found 29 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.
When is the next survey likely?
Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.
A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured
Get an email about KADIMA REHABILITATION & NURSING AT HARMONY
One email when it happens. No account; stop it any time with one click.
7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.
Emergency preparedness
8 of the 55 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index
Physical environment (health survey)
9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 55 Life Safety citations above. The Physical Environment Index
- F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
- F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
- F-0880 Provide and implement an infection prevention and control program.
- F-0926 Have policies on smoking.
How that compares
Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.
| Measure | Citations |
|---|---|
| This facility | 55 |
| Median facility in PA | 10 |
| Median facility nationally | 11 |
Survey history
| Survey date | Citations |
|---|---|
| June 9, 2023 | 10 |
| May 3, 2024 | 16 |
| May 9, 2025 | 29 |
Most-cited tags
| Tag | What the surveyor checks | Times cited | Last cited |
|---|---|---|---|
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 3 | 2025-05-09 |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | 3 | 2025-05-09 |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | 2 | 2025-05-09 |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | 2 | 2025-05-09 |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | 2 | 2025-05-09 |
| K-0712 | Have simulated fire drills held at unexpected times. | 2 | 2025-05-09 |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 2 | 2025-05-09 |
| K-0920 | Ensure proper usage of power strips and extension cords. | 2 | 2024-05-03 |
What the citations cover
- Smoke Deficiencies 13
- Gas, Vacuum, and Electrical Systems Deficiencies 11
- Egress Deficiencies 9
- Emergency Preparedness Deficiencies 8
- Other 14
| Category | Citations |
|---|---|
| Smoke Deficiencies | 13 |
| Gas, Vacuum, and Electrical Systems Deficiencies | 11 |
| Egress Deficiencies | 9 |
| Emergency Preparedness Deficiencies | 8 |
| Construction Deficiencies | 5 |
| Miscellaneous Deficiencies | 5 |
| Services Deficiencies | 4 |
Every citation on file
As published by CMS, newest survey first. Descriptions are CMS’s own wording.
May 9, 2025 — 29 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| E-0006 | Conduct risk assessment and an All-Hazards approach. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0015 | Address subsistence needs for staff and patients. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0020 | Establish policies and procedures including evacuation. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0023 | Establish policies and procedures for medical documentation. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0032 | Provide primary/alternate means for communication. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0035 | Provide family notifications of emergency plan. | Deficient, Provider has plan of correction (July 14, 2025) |
| E-0036 | Establish emergency prep training and testing. | Deficient, Provider has date of correction (August 6, 2025) |
| E-0041 | Implement emergency and standby power systems. | Deficient, Provider has plan of correction (July 14, 2025) |
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0111 | Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0133 | Install a two-hour-resistant firewall separation. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0223 | Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0225 | Have stairways and smokeproof enclosures used as exits that meet safety requirements. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0271 | Have exits that are accessible at all times. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0311 | Have an enclosure around a vertical opening shaft. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0355 | Properly select, install, inspect, or maintain portable fire extinguishes. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0363 | Install corridor and hallway doors that block smoke. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0372 | Ensure smoke barriers are constructed to a 1 hour fire resistance rating. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has plan of correction (July 12, 2025) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (August 6, 2025) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has plan of correction (July 12, 2025) |
May 3, 2024 — 16 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0100 | Meet other general requirements. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0200 | Meet other general requirements. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0293 | Have properly located and lighted "Exit" signs. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0324 | Provide properly protected cooking facilities. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0345 | Have approved installation, maintenance and testing program for fire alarm systems. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0500 | Meet other general requirements that are deficient. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (July 1, 2024) |
| K-0712 | Have simulated fire drills held at unexpected times. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0741 | Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0754 | Provide properly sized and located linen or trash receptacles. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0911 | Meet requirements for the installation and maintenance of electrical systems. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0912 | Have power receptacles that are properly grounded. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (June 4, 2024) |
| K-0923 | Have proper medical gas storage and administration areas. | Deficient, Provider has date of correction (June 4, 2024) |
June 9, 2023 — 10 citations
| Tag | What the surveyor checks | Status |
|---|---|---|
| K-0161 | Use approved construction type or materials. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0222 | Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0231 | Provide large enough exits. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0291 | Install emergency lighting that can last at least 1 1/2 hours. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0353 | Inspect, test, and maintain automatic sprinkler systems. | Deficient, Provider has date of correction (August 30, 2023) |
| K-0374 | Install smoke barrier doors that can resist smoke for at least 20 minutes. | Deficient, Provider has date of correction (August 30, 2023) |
| K-0521 | Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0914 | Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0918 | Have generator or other power source capable of supplying service within 10 seconds. | Deficient, Provider has date of correction (July 29, 2023) |
| K-0920 | Ensure proper usage of power strips and extension cords. | Deficient, Provider has date of correction (July 29, 2023) |
Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.