Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

KADIMA REHABILITATION & NURSING AT HARMONY

HARMONY, PA · 115 certified beds · Last Life Safety survey May 9, 2025

CMS Certification Number 395758 · first certified June 1988

Ownership

Operated by KADIMA HEALTHCARE GROUP · For profit - Limited Liability company

No change of ownership on CMS record since January 1, 2016, when the records begin.

55
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
14
Tags cited more than once
Across separate surveys
20
Inspection & testing records
Of the citations on file

Position within PA

55 citations — more than 100% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 29 citations; the earlier surveys in the window averaged 13. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about KADIMA REHABILITATION & NURSING AT HARMONY

One email when it happens. No account; stop it any time with one click.

Which alerts

7 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

8 of the 55 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 55 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0926 Have policies on smoking.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility55PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility55
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
102023-06162024-05292025-05
Citations at each Life Safety survey
Survey dateCitations
June 9, 202310
May 3, 202416
May 9, 202529

Most-cited tags

Most-cited tags at this facility
K-05213K-03533K-03452K-09182K-09112K-07122K-07412K-09202
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.32025-05-09
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-05-09
K-0345Have approved installation, maintenance and testing program for fire alarm systems.22025-05-09
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-05-09
K-0911Meet requirements for the installation and maintenance of electrical systems.22025-05-09
K-0712Have simulated fire drills held at unexpected times.22025-05-09
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.22025-05-09
K-0920Ensure proper usage of power strips and extension cords.22024-05-03

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 13
  • Gas, Vacuum, and Electrical Systems Deficiencies 11
  • Egress Deficiencies 9
  • Emergency Preparedness Deficiencies 8
  • Other 14
Citations by CMS category
CategoryCitations
Smoke Deficiencies13
Gas, Vacuum, and Electrical Systems Deficiencies11
Egress Deficiencies9
Emergency Preparedness Deficiencies8
Construction Deficiencies5
Miscellaneous Deficiencies5
Services Deficiencies4

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 9, 2025 — 29 citations

Citations issued on May 9, 2025
TagWhat the surveyor checksStatus
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has plan of correction (July 14, 2025)
E-0015Address subsistence needs for staff and patients.Deficient, Provider has plan of correction (July 14, 2025)
E-0020Establish policies and procedures including evacuation.Deficient, Provider has plan of correction (July 14, 2025)
E-0023Establish policies and procedures for medical documentation.Deficient, Provider has plan of correction (July 14, 2025)
E-0032Provide primary/alternate means for communication.Deficient, Provider has plan of correction (July 14, 2025)
E-0035Provide family notifications of emergency plan.Deficient, Provider has plan of correction (July 14, 2025)
E-0036Establish emergency prep training and testing.Deficient, Provider has date of correction (August 6, 2025)
E-0041Implement emergency and standby power systems.Deficient, Provider has plan of correction (July 14, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 6, 2025)
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has plan of correction (July 12, 2025)
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has plan of correction (July 12, 2025)
K-0223Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.Deficient, Provider has plan of correction (July 12, 2025)
K-0225Have stairways and smokeproof enclosures used as exits that meet safety requirements.Deficient, Provider has date of correction (August 6, 2025)
K-0271Have exits that are accessible at all times.Deficient, Provider has date of correction (August 6, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has plan of correction (July 12, 2025)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (August 6, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 6, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 6, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 6, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 6, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 6, 2025)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has plan of correction (July 12, 2025)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (August 6, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has plan of correction (July 12, 2025)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (August 6, 2025)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has plan of correction (July 12, 2025)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has plan of correction (July 12, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 6, 2025)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has plan of correction (July 12, 2025)

May 3, 2024 — 16 citations

Citations issued on May 3, 2024
TagWhat the surveyor checksStatus
K-0100Meet other general requirements.Deficient, Provider has date of correction (June 4, 2024)
K-0200Meet other general requirements.Deficient, Provider has date of correction (June 4, 2024)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (June 4, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (June 4, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (June 4, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (June 4, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (June 4, 2024)
K-0500Meet other general requirements that are deficient.Deficient, Provider has date of correction (June 4, 2024)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 1, 2024)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (June 4, 2024)
K-0741Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.Deficient, Provider has date of correction (June 4, 2024)
K-0754Provide properly sized and located linen or trash receptacles.Deficient, Provider has date of correction (June 4, 2024)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (June 4, 2024)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (June 4, 2024)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 4, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (June 4, 2024)

June 9, 2023 — 10 citations

Citations issued on June 9, 2023
TagWhat the surveyor checksStatus
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (July 29, 2023)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (July 29, 2023)
K-0231Provide large enough exits.Deficient, Provider has date of correction (July 29, 2023)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (July 29, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 30, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 30, 2023)
K-0521Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.Deficient, Provider has date of correction (July 29, 2023)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (July 29, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (July 29, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (July 29, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.