Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

GARVEY MANOR

HOLLIDAYSBURG, PA · 132 certified beds · Last Life Safety survey June 4, 2026

CMS Certification Number 395050 · first certified January 1967

Ownership

Operated by CARMELITE SISTERS FOR THE AGED & INFIRM · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

20
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
5
Tags cited more than once
Across separate surveys
8
Inspection & testing records
Of the citations on file

Position within PA

20 citations — more than 82% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Holding steadyabout the same at the latest survey as at its earlier surveys in the window.

The latest survey found 0 citations; the earlier surveys in the window averaged 10. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens April 2027 — about 7 months from now. This facility’s last Life Safety survey was June 2026. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about GARVEY MANOR

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

2 of the 20 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

4 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 20 Life Safety citations above. The Physical Environment Index

  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility20PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility20
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
102023-08102024-0802026-06
Citations at each Life Safety survey
Survey dateCitations
August 3, 202310
August 1, 202410
June 4, 20260

Most-cited tags

Most-cited tags at this facility
K-03532K-09182E-00412K-03212K-03722K-02111K-03521K-09111
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-08-01
K-0918Have generator or other power source capable of supplying service within 10 seconds.22024-08-01
E-0041Implement emergency and standby power systems.22024-08-01
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22024-08-01
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.22024-08-01
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.12023-08-03
K-0352Properly install and monitor supervisory attachments on automatic sprinkler systems.12024-08-01
K-0911Meet requirements for the installation and maintenance of electrical systems.12023-08-03

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 11
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Emergency Preparedness Deficiencies 2
  • Egress Deficiencies 1
  • Other 1
Citations by CMS category
CategoryCitations
Smoke Deficiencies11
Gas, Vacuum, and Electrical Systems Deficiencies5
Emergency Preparedness Deficiencies2
Egress Deficiencies1
Construction Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

August 1, 2024 — 10 citations

Citations issued on August 1, 2024
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (September 28, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (September 28, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 28, 2024)
K-0352Properly install and monitor supervisory attachments on automatic sprinkler systems.Deficient, Provider has date of correction (September 28, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 28, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 28, 2024)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 28, 2024)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (September 28, 2024)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (September 28, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (September 28, 2024)

August 3, 2023 — 10 citations

Citations issued on August 3, 2023
TagWhat the surveyor checksStatus
E-0041Implement emergency and standby power systems.Deficient, Provider has date of correction (October 21, 2023)
K-0131Meet requirements for sections of health care facilities separated by fire resistive construction.Deficient, Provider has date of correction (October 21, 2023)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (October 21, 2023)
K-0311Have an enclosure around a vertical opening shaft.Deficient, Provider has date of correction (October 21, 2023)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 21, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (October 21, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (October 21, 2023)
K-0911Meet requirements for the installation and maintenance of electrical systems.Deficient, Provider has date of correction (October 21, 2023)
K-0912Have power receptacles that are properly grounded.Deficient, Provider has date of correction (October 21, 2023)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 21, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.