Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

WECARE AT SYCAMORE REHABILITATION AND NURSING CENT

MONTOURSVILLE, PA · 133 certified beds · Last Life Safety survey March 13, 2026

CMS Certification Number 395379 · first certified October 1978

Ownership

Operated by WECARE CENTERS · For profit - Limited Liability company

  • Ownership changed November 17, 2022 (change of ownership)to WECARE AT LOYALSOCK REHABILITATION AND NURSING CENTER from EMBASSY LOYALSOCK, LLC
21
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
3
Tags cited more than once
Across separate surveys
10
Inspection & testing records
Of the citations on file

Position within PA

21 citations — more than 84% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 10 citations; the earlier surveys in the window averaged 5.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

The window opens January 2027 — about 4 months from now. This facility’s last Life Safety survey was March 2026. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about WECARE AT SYCAMORE REHABILITATION AND NURSING CENT

One email when it happens. No account; stop it any time with one click.

Which alerts

2 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

8 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 21 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0908 Keep all essential equipment working safely.
  • F-0909 Regularly inspect all bed frames, mattresses, and bed rails (if any) for safety; and all bed rails and mattresses must attach safely to the bed frame.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility21PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility21
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
72024-0342025-02102026-03
Citations at each Life Safety survey
Survey dateCitations
March 15, 20247
February 21, 20254
March 13, 202610

Most-cited tags

Most-cited tags at this facility
K-03633K-03533K-03212K-07611K-01331K-09191K-05411K-03241
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0363Install corridor and hallway doors that block smoke.32026-03-13
K-0353Inspect, test, and maintain automatic sprinkler systems.32026-03-13
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.22026-03-13
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.12025-02-21
K-0133Install a two-hour-resistant firewall separation.12024-03-15
K-0919Meet requirements for the use of electrical equipment.12024-03-15
K-0541Install properly constructed and protected linen or trash chutes.12026-03-13
K-0324Provide properly protected cooking facilities.12026-03-13

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 12
  • Construction Deficiencies 2
  • Egress Deficiencies 2
  • Gas, Vacuum, and Electrical Systems Deficiencies 2
  • Other 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies12
Construction Deficiencies2
Egress Deficiencies2
Gas, Vacuum, and Electrical Systems Deficiencies2
Miscellaneous Deficiencies2
Services Deficiencies1

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

March 13, 2026 — 10 citations

Citations issued on March 13, 2026
TagWhat the surveyor checksStatus
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (April 28, 2026)
K-0222Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.Deficient, Provider has date of correction (April 28, 2026)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (April 28, 2026)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (April 28, 2026)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (April 28, 2026)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 28, 2026)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 28, 2026)
K-0541Install properly constructed and protected linen or trash chutes.Deficient, Provider has date of correction (April 28, 2026)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (April 28, 2026)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (April 28, 2026)

February 21, 2025 — 4 citations

Citations issued on February 21, 2025
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (April 3, 2025)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (April 3, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (April 3, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (April 3, 2025)

March 15, 2024 — 7 citations

Citations issued on March 15, 2024
TagWhat the surveyor checksStatus
K-0133Install a two-hour-resistant firewall separation.Deficient, Provider has date of correction (May 7, 2024)
K-0161Use approved construction type or materials.Deficient, Provider has date of correction (May 7, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (May 7, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 7, 2024)
K-0362Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.Deficient, Provider has date of correction (May 7, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (May 7, 2024)
K-0919Meet requirements for the use of electrical equipment.Deficient, Provider has date of correction (May 7, 2024)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.