Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

KADIMA REHABILITATION & NURSING AT CAMPBELLTOWN

PALMYRA, PA · 53 certified beds · Last Life Safety survey June 6, 2025

CMS Certification Number 395846 · first certified April 1991

Ownership

Operated by KADIMA HEALTHCARE GROUP · For profit - Limited Liability company

  • Ownership changed August 29, 2018 (change of ownership)from MAYBROOK-P TWIN OAKS OPCO LLC
32
Citations on file
Rolling three-year window
5
Life Safety surveys
In the same window
7
Tags cited more than once
Across separate surveys
19
Inspection & testing records
Of the citations on file

Position within PA

32 citations — more than 96% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Slippingmore citations at the latest survey than at its earlier surveys in the window.

The latest survey found 14 citations; the earlier surveys in the window averaged 4.5. With 5 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (April 2026 to June 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was June 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about KADIMA REHABILITATION & NURSING AT CAMPBELLTOWN

One email when it happens. No account; stop it any time with one click.

Which alerts

5 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Emergency preparedness

3 of the 32 citations on file are Emergency Preparedness E-tags. E-tags are cited under 42 CFR §483.73 and concern the emergency plan, training, drills, communications and supplies. Nationally about half of certified facilities have at least one. The Emergency Preparedness Index

Physical environment (health survey)

9 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 32 Life Safety citations above. The Physical Environment Index

  • F-0584 Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.
  • F-0880 Provide and implement an infection prevention and control program.
  • F-0925 Make sure there is a pest control program to prevent/deal with mice, insects, or other pests.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility32PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility32
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
32023-0812024-04122024-0722025-03142025-06
Citations at each Life Safety survey
Survey dateCitations
August 30, 20233
April 9, 20241
July 18, 202412
March 6, 20252
June 6, 202514

Most-cited tags

Most-cited tags at this facility
K-03454K-03533K-01002K-03242E-00042K-09182K-03552K-02911
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0345Have approved installation, maintenance and testing program for fire alarm systems.42025-06-06
K-0353Inspect, test, and maintain automatic sprinkler systems.32025-06-06
K-0100Meet other general requirements.22025-06-06
K-0324Provide properly protected cooking facilities.22025-06-06
E-0004Develop and maintain an Emergency Preparedness Program (EP).22025-06-06
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-06-06
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.22025-06-06
K-0291Install emergency lighting that can last at least 1 1/2 hours.12025-06-06

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 15
  • Gas, Vacuum, and Electrical Systems Deficiencies 5
  • Egress Deficiencies 4
  • Emergency Preparedness Deficiencies 3
  • Other 5
Citations by CMS category
CategoryCitations
Smoke Deficiencies15
Gas, Vacuum, and Electrical Systems Deficiencies5
Egress Deficiencies4
Emergency Preparedness Deficiencies3
Construction Deficiencies3
Miscellaneous Deficiencies2

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

June 6, 2025 — 14 citations

Citations issued on June 6, 2025
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (August 21, 2025)
K-0100Meet other general requirements.Deficient, Provider has date of correction (August 21, 2025)
K-0211Keep aisles, corridors, and exits free of obstruction in case of emergency.Deficient, Provider has date of correction (August 21, 2025)
K-0291Install emergency lighting that can last at least 1 1/2 hours.Deficient, Provider has date of correction (August 21, 2025)
K-0293Have properly located and lighted "Exit" signs.Deficient, Provider has date of correction (August 21, 2025)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (August 21, 2025)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (August 21, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 21, 2025)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (August 21, 2025)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (August 21, 2025)
K-0712Have simulated fire drills held at unexpected times.Deficient, Provider has date of correction (August 21, 2025)
K-0761To conduct inspection, testing and maintenance of fire doors by qualified individuals.Deficient, Provider has date of correction (August 21, 2025)
K-0914Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.Deficient, Provider has date of correction (August 21, 2025)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 21, 2025)

March 6, 2025 — 2 citations

Citations issued on March 6, 2025
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (May 2, 2025)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (May 2, 2025)

July 18, 2024 — 12 citations

Citations issued on July 18, 2024
TagWhat the surveyor checksStatus
E-0004Develop and maintain an Emergency Preparedness Program (EP).Deficient, Provider has date of correction (October 16, 2024)
E-0006Conduct risk assessment and an All-Hazards approach.Deficient, Provider has date of correction (October 16, 2024)
K-0100Meet other general requirements.Deficient, Provider has date of correction (September 17, 2024)
K-0226Have horizontal exits used in accordance with safety requirements.Deficient, Provider has date of correction (September 17, 2024)
K-0321Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.Deficient, Provider has date of correction (October 16, 2024)
K-0324Provide properly protected cooking facilities.Deficient, Provider has date of correction (September 17, 2024)
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (October 16, 2024)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 17, 2024)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 17, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (October 16, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (October 16, 2024)
K-0923Have proper medical gas storage and administration areas.Deficient, Provider has date of correction (October 16, 2024)

April 9, 2024 — 1 citation

Citations issued on April 9, 2024
TagWhat the surveyor checksStatus
K-0111Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.Deficient, Provider has date of correction (May 30, 2024)

August 30, 2023 — 3 citations

Citations issued on August 30, 2023
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 9, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 9, 2023)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (September 9, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.