Federal nursing home survey record · CMS-certified nursing home· Not a state assisted-living licensing record

Vincentian Home

PITTSBURGH, PA · 106 certified beds · Last Life Safety survey May 2, 2025

CMS Certification Number 395034 · first certified January 1967

Ownership

Independently operated (no chain recorded by CMS) · Non profit - Corporation

No change of ownership on CMS record since January 1, 2016, when the records begin.

11
Citations on file
Rolling three-year window
3
Life Safety surveys
In the same window
3
Tags cited more than once
Across separate surveys
9
Inspection & testing records
Of the citations on file

Position within PA

11 citations — more than 51% of the 656 certified nursing homes in PA. Compared within PA rather than nationally because which state a facility is in explains about 30% of the variation in citation counts between facilities, while bed count explains under 1%. State survey agencies differ far more than the buildings do. How this is calculated

Improvingfewer citations at the latest survey than at its earlier surveys in the window.

The latest survey found 2 citations; the earlier surveys in the window averaged 4.5. With 3 surveys on file this is a direction of travel, not a conclusion.

When is the next survey likely?

Well past the typical window (March 2026 to May 2026), and past the point by which nine in ten PA facilities have been surveyed. This facility’s last Life Safety survey was May 2025. Facilities in PA are typically surveyed 10–12 months after the last one (median 11), measured over 1,113 consecutive surveys in the last two years of CMS records.

A range the record supports, not a prediction of a date. State agencies vary widely — from about 11 months in Pennsylvania to three years in Maryland. How the window is measured

Get an email about Vincentian Home

One email when it happens. No account; stop it any time with one click.

Which alerts

3 inspection-and-testing tags have been cited here at more than one survey. Nationally, that pattern is common: about three quarters of cited facilities have at least one repeated tag, and half of the facilities ever cited for sprinkler inspection and testing are cited for it again. A repeat is usually a recordkeeping gap rather than a new hazard.

Physical environment (health survey)

6 physical-environment citations on the health survey. Cited by the health surveyors under Appendix PP, not the Life Safety Code surveyor: equipment in safe operating condition, the call system, bed rails, pest control, hazards, the environment. Counted separately from the 11 Life Safety citations above. The Physical Environment Index

  • F-0880 Provide and implement an infection prevention and control program.
  • F-0908 Keep all essential equipment working safely.
  • F-0689 Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

How that compares

Citations on file over three years

Compared with the median facility in PA, and nationally. Surveyors differ markedly between states, so the PA figure is the meaningful one.

This facility11PA median10National median11
Citations on file over three years, compared
MeasureCitations
This facility11
Median facility in PA10
Median facility nationally11

Survey history

Citations at each Life Safety survey
62023-0732024-0522025-05
Citations at each Life Safety survey
Survey dateCitations
July 21, 20236
May 31, 20243
May 2, 20252

Most-cited tags

Most-cited tags at this facility
K-09182K-03632K-03532K-03721K-03551K-03451K-03741K-09201
Most-cited tags at this facility
TagWhat the surveyor checksTimes citedLast cited
K-0918Have generator or other power source capable of supplying service within 10 seconds.22025-05-02
K-0363Install corridor and hallway doors that block smoke.22024-05-31
K-0353Inspect, test, and maintain automatic sprinkler systems.22024-05-31
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.12023-07-21
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.12023-07-21
K-0345Have approved installation, maintenance and testing program for fire alarm systems.12023-07-21
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.12023-07-21
K-0920Ensure proper usage of power strips and extension cords.12025-05-02

What the citations cover

Citations by CMS category
  • Smoke Deficiencies 8
  • Gas, Vacuum, and Electrical Systems Deficiencies 3
Citations by CMS category
CategoryCitations
Smoke Deficiencies8
Gas, Vacuum, and Electrical Systems Deficiencies3

Every citation on file

As published by CMS, newest survey first. Descriptions are CMS’s own wording.

May 2, 2025 — 2 citations

Citations issued on May 2, 2025
TagWhat the surveyor checksStatus
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (June 23, 2025)
K-0920Ensure proper usage of power strips and extension cords.Deficient, Provider has date of correction (June 23, 2025)

May 31, 2024 — 3 citations

Citations issued on May 31, 2024
TagWhat the surveyor checksStatus
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (August 1, 2024)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (August 1, 2024)
K-0918Have generator or other power source capable of supplying service within 10 seconds.Deficient, Provider has date of correction (August 1, 2024)

July 21, 2023 — 6 citations

Citations issued on July 21, 2023
TagWhat the surveyor checksStatus
K-0345Have approved installation, maintenance and testing program for fire alarm systems.Deficient, Provider has date of correction (September 4, 2023)
K-0353Inspect, test, and maintain automatic sprinkler systems.Deficient, Provider has date of correction (September 4, 2023)
K-0355Properly select, install, inspect, or maintain portable fire extinguishes.Deficient, Provider has date of correction (September 4, 2023)
K-0363Install corridor and hallway doors that block smoke.Deficient, Provider has date of correction (September 4, 2023)
K-0372Ensure smoke barriers are constructed to a 1 hour fire resistance rating.Deficient, Provider has date of correction (September 4, 2023)
K-0374Install smoke barrier doors that can resist smoke for at least 20 minutes.Deficient, Provider has date of correction (October 5, 2023)

Reflects the CMS posting of August 1, 2026. Surveys conducted in the last few months may not appear yet.